ADL400 is a smart meter designed for power supply system, industrial and mining enterprises and utilities to calculate the electricity consumption and manage the electric demand. It features the high precision, small size and simple installation. It integrates the measurement of all electrical parameters with the comprehensive electricity metering and management provides various data on previous 48 months, checks the 31st harmonic content and the total harmonic content. It is fitted with RS485 communication port and adapted to MODBUS-RTU .ADL400 can be used in all kinds of control systems, SCADA systems and energy management systems. The meter meet the related technical requirements of electricity meter in the IEC62053-21standards.
Measurement:3-phase AC kWh, kVarh
Measurement:U,1, P, Q, S, PF, F and etc
Display:LCD Display
HMI:Keypads Programming
Communication:RS485 (MODBUS-RTU)
Multi-rate/tariff:4 Tariff Rates and etc
Harmonic:2~31st&Total Harmonic
Data Function:Data Fronzen, Max Demand
Rated Voltage:100~120 or 380~456Vac L-L1(6)A AC; 10(80)A AC
Rated Current:1(6)A AC; 10(80)A AC
Frequency:45~65 Hz
Wiring:3-phase 3-wire/4wire
Accuracy:0.5%(kWh
Temperature:-25°C~+55°C
Humidity:≤95% RH
Altitude:≤2500m
Dimension of ADL400 </br>(Current Input via Direct Connect)
Dimension of ADL400</br>(Current Input via CTs)
ADL400 is a smart meter designed for power supply system, industrial and mining enterprises and utilities to calculate the electricity consumption and manage the electric demand. It features the high precision, small size and simple installation.
Output
RS485 (MODBUS-RTU) Multi-rate/tariff: 4 Tariff Rates and etc Harmonic: 2~31st&Total Harmonic Data Function: Data Fronzen, Max Demand
Modbus-RTU into your EMS / SCADA
System voltage
100~120 or 380~456Vac L-L1(6)A AC; 10(80)A AC
Frequency
45~65 Hz Wiring: 3-phase 3-wire/4wire
| Parameter | Value |
|---|---|
| Measurement | 3-phase AC kWh, kVarh Measurement: U,1, P, Q, S, PF, F and etc |
| Display | LCD |
| Display HMI | Keypads Programming |
| Rated Current | 1(6)A AC; 10(80)A AC |
| Accuracy | 0.5%(kWh Temperature:-25°C~+55°C |
| Humidity | ≤95% RH |
| Altitude | ≤2500m |
Ask us about this model. Send us the rated values of your circuit and the supply voltage; we confirm the ordering code, wiring diagram and register list within one working day.
1.Technical parameter
1.1 Electrical performance
| Specification | 3 phase 3 wires | 3 phase 4 wires | ||
|
Measurement | Voltage | Reference voltage | 3×100V, 3×380V | 3×57.7/100V, 3×220/380V |
| Voltage range | 3×100V – 3×450V | 3×57.7/100V – 3×260/450V | ||
| Consumption | <10VA(Single phase) | |||
| Impedance | >2MΩ | |||
| Accuracy class | Error±0.2% | |||
| Current | Input current | 3×1(6)A, 3×10(80)A | ||
| Consumption | <1VA Single phase rated current | |||
| Accuracy class | Error±0.2% | |||
| Power | Active, reactive, apparent power, error±0.5% | |||
| Frequency | 45~65Hz, Error±0.2% | |||
| Metering | Energy | Active energy(Accuracy class: 0.5); reactive energy(Accuracy class 2) | ||
| Clock | ≤0.5s/d | |||
| Digit signal | Energy pulse output | 1 active photocoupler output | ||
| Pulse | Width of pulse | 80±20ms | ||
| Pulse constant | 400imp/kWh,10000imp/kWh(Correspond with the basic current) | |||
| Communication | Interface and communication protocol | RS485: Modbus RTU | ||
| Range of communication address | Modbus RTU: 1~ 254 | |||
| Baud rate | 1200bps~38400bps | |||
1.2 Work Environment
| Environment | working temperature | -25℃~+55℃ |
| Relative humidity | ≤95%(No condensation) |
2. Basic & Optional Function
| Function | Function description | Function provide |
| Measurement of kWh | Active kWh (positive and negative) | ■ |
| Reactive kWh (positive and negative) | ■ | |
| A. B, C split phase positive active energy | ■ | |
| Measurement of electrical parameters | U, I | ■ |
| P, Q, S , PF, F | ■ | |
| Measurement of harmonics | 2~31 Voltage and current harmonic | ■ |
| LCD Display | 12 bits section LCD display, background light | ■ |
| Key programming | 3 keys to communication and set parameters | ■ |
| Pulse output | Active pulse output | ■ |
| Multi-tariff and functions | Adapt 4 time zones, 2 time interval lists, 14 time interval by day and 4 tariff rates | □ |
| Max demanded kWh and time happened | □ | |
| Frozen data on last 48 months, last 90days | □ | |
| Date, time | □ | |
| Communication | Interface: RS485, Protocol: MODBUS-RTU | ■ |
"■" means standard, "□" means optional.