Communication
RS485 Communication
Modbus-RTU Protocol
Baud Rate: 1200–38400bps
Display
LCD Display
System Time Display
Parameter Setting and Control via Keys
Rated U and l
Three-phase Four-wire
Rated Voltage: AC 3×57.7V/100V, AC 3×220V/380V, AC 3×380V/660V
Rated Current: AC 1A or 5A
Frequency: 45–65Hz
Voltage Overload: 1.2× continuous, 2× for 1s
Current Overload: 1.2× continuous, 10× for 1s
AMC96L-E4/KC is a 96-size panel-mounted multifunction power meter designed for electrical parameter measurement, energy metering and power monitoring in three-phase four-wire systems. It measures three-phase voltage and current, zero-sequence voltage and current, active, reactive and apparent power, power factor, frequency, voltage phase angle, voltage/current unbalance, forward and reverse power and four-quadrant energy.
Accuracy
Voltage & Current: Class 0.2
Active Power: Class 0.5
Reactive Power: Class 1.0
Active Energy: Class 0.5
Reactive Energy: Class 1.0
Frequency: 0.05Hz
Frequency
45–65Hz
Electrical Measurement
Three-phase voltage and zero-sequence voltage
Three-phase current and zero-sequence current
Three-phase and total active power
Three-phase and total reactive power
Three-phase and total apparent power
Three-phase and total power factor
Frequency
Voltage phase angle
Voltage and current unbalance
Forward and reverse power
Energy Measurement
Four-quadrant energy metering
System time display
Communication
RS485 Communication
Modbus-RTU Protocol
Baud Rate: 1200–38400bps
Input & Output
4DI + 2DO + 1 Energy Pulse
or
2DI + 2DO + 1 Energy Pulse
Switching Input
Dry contact input
Built-in power supply
Relay Output
Normally open contact
AC 250V / 3A
DC 30V / 3A
Optional Function
Multi-tariff Energy Metering optional
2nd–31st Harmonic Measurement optional
1-channel Analog Output optional
2-channel Analog Output optional
Auxiliary Power Supply
AC/DC 85–265V
DC 24V (±20%) optional supply
DC 48V (±20%) optional supply
Power Consumption ≤10VA
Environment
Operating Temperature: -25°C to +65°C
Storage Temperature: -40°C to +80°C
Relative Humidity: ≤93%RH, non-condensing
Altitude: ≤2500m
| Item | Specification |
|---|---|
| Wiring | Three-phase Four-wire |
| Frequency | 45–65Hz |
| Rated Voltage | AC 3×57.7/100V, 3×220/380V, 3×380/660V |
| Voltage Overload | 1.2× continuous; 2× for 1s |
| Voltage Consumption | <0.5VA |
| Rated Current | AC 1A / 5A |
| Current Overload | 1.2× continuous; 10× for 1s |
| Current Consumption | <0.5VA |
| Voltage Accuracy | Class 0.2 |
| Current Accuracy | Class 0.2 |
| Active Power Accuracy | Class 0.5 |
| Reactive Power Accuracy | Class 1.0 |
| Active Energy Accuracy | Class 0.5 |
| Reactive Energy Accuracy | Class 1.0 |
| Frequency Accuracy | 0.05Hz |
| Communication | RS485 |
| Protocol | Modbus-RTU |
| Baud Rate | 1200–38400bps |
| Relay Contact | AC 250V/3A, DC 30V/3A |
| Pulse Constant | 10000 imp/kWh, settable |
| Analog Output | 4–20mA, optional |
| Auxiliary Power | AC/DC 85–265V |
| Operating Temperature | -25°C to +65°C |
| Storage Temperature | -40°C to +80°C |
| Humidity | ≤93%RH, non-condensing |
| Altitude | ≤2500m |
| Function | AMC96L-E4/KC |
|---|---|
| Three-phase Voltage | ✓ |
| Zero-sequence Voltage | ✓ |
| Three-phase Current | ✓ |
| Zero-sequence Current | ✓ |
| Three-phase Active Power | ✓ |
| Total Active Power | ✓ |
| Three-phase Reactive Power | ✓ |
| Total Reactive Power | ✓ |
| Three-phase Apparent Power | ✓ |
| Total Apparent Power | ✓ |
| Three-phase Power Factor | ✓ |
| Total Power Factor | ✓ |
| Frequency | ✓ |
| Voltage Phase Angle | ✓ |
| Voltage Unbalance | ✓ |
| Current Unbalance | ✓ |
| Forward / Reverse Power | ✓ |
| Four-quadrant Energy Metering | ✓ |
| System Time Display | ✓ |
| RS485 | ✓ |
| Modbus-RTU | ✓ |
| 4DI + 2DO + 1 Energy Pulse | Optional |
| 2DI + 2DO + 1 Energy Pulse | Optional |
| Multi-tariff Energy Metering | Optional |
| 2nd–31st Harmonic Measurement | Optional |
| 2-channel Analog Output | Optional |
| 1-channel Analog Output | Optional |
| 2DI (AC 220V) + 2DO + 1 Energy Pulse | Optional |