head_banner_pro

AMC96L-E4/KC Multifunction Panel Power Meter

Application:

1) Multifunction three-phase power monitoring for low-voltage distribution systems
2) Measures voltage, current, active power, reactive power, apparent power, power factor and frequency
3) Supports four-quadrant energy metering, voltage/current unbalance and phase angle monitoring
4) Suitable for switchgear, distribution cabinets, industrial facilities, commercial buildings and energy management systems

Basic Parameters:

1) Wiring: three-phase four-wire
2) Rated voltage: AC 3×57.7/100V, 3×220/380V or 3×380/660V
3) Rated current: AC 1A or 5A
4) Accuracy: voltage/current Class 0.2; active power Class 0.5; active energy Class 0.5
5) Communication: RS485, Modbus-RTU
6) I/O: 4DI+2DO+1 energy pulse or 2DI+2DO+1 energy pulse
7) Auxiliary power: AC/DC 85–265V
8) Panel size: 96×96mm; cut-out size: 88×88mm


Information

Parameter

Function

Download

Characteristic

5

Communication

RS485 Communication
Modbus-RTU Protocol
Baud Rate: 1200–38400bps

6

Display
LCD Display
System Time Display
Parameter Setting and Control via Keys

7

Rated U and l
Three-phase Four-wire
Rated Voltage: AC 3×57.7V/100V, AC 3×220V/380V, AC 3×380V/660V
Rated Current: AC 1A or 5A
Frequency: 45–65Hz
Voltage Overload: 1.2× continuous, 2× for 1s
Current Overload: 1.2× continuous, 10× for 1s

General

AMC96L-E4/KC is a 96-size panel-mounted multifunction power meter designed for electrical parameter measurement, energy metering and power monitoring in three-phase four-wire systems. It measures three-phase voltage and current, zero-sequence voltage and current, active, reactive and apparent power, power factor, frequency, voltage phase angle, voltage/current unbalance, forward and reverse power and four-quadrant energy.

Function

Accuracy

Voltage & Current: Class 0.2
Active Power: Class 0.5
Reactive Power: Class 1.0
Active Energy: Class 0.5
Reactive Energy: Class 1.0
Frequency: 0.05Hz

Frequency

45–65Hz

Electrical Measurement

Three-phase voltage and zero-sequence voltage
Three-phase current and zero-sequence current
Three-phase and total active power
Three-phase and total reactive power
Three-phase and total apparent power
Three-phase and total power factor
Frequency
Voltage phase angle
Voltage and current unbalance
Forward and reverse power

Energy Measurement

Four-quadrant energy metering
System time display

HG9A9446
HG9A9685

Communication

RS485 Communication
Modbus-RTU Protocol
Baud Rate: 1200–38400bps

Input & Output

4DI + 2DO + 1 Energy Pulse
or
2DI + 2DO + 1 Energy Pulse

Switching Input

Dry contact input
Built-in power supply

Relay Output

Normally open contact
AC 250V / 3A
DC 30V / 3A

Optional Function

Multi-tariff Energy Metering optional
2nd–31st Harmonic Measurement optional
1-channel Analog Output optional
2-channel Analog Output optional

Auxiliary Power Supply

AC/DC 85–265V
DC 24V (±20%) optional supply
DC 48V (±20%) optional supply
Power Consumption ≤10VA

Environment

Operating Temperature: -25°C to +65°C
Storage Temperature: -40°C to +80°C
Relative Humidity: ≤93%RH, non-condensing
Altitude: ≤2500m

Wiring

amc96_wiring

Installation

amc96_installation

Typical connection

8

  • Previous:
  • Next:

  • Item Specification
    Wiring Three-phase Four-wire
    Frequency 45–65Hz
    Rated Voltage AC 3×57.7/100V, 3×220/380V, 3×380/660V
    Voltage Overload 1.2× continuous; 2× for 1s
    Voltage Consumption <0.5VA
    Rated Current AC 1A / 5A
    Current Overload 1.2× continuous; 10× for 1s
    Current Consumption <0.5VA
    Voltage Accuracy Class 0.2
    Current Accuracy Class 0.2
    Active Power Accuracy Class 0.5
    Reactive Power Accuracy Class 1.0
    Active Energy Accuracy Class 0.5
    Reactive Energy Accuracy Class 1.0
    Frequency Accuracy 0.05Hz
    Communication RS485
    Protocol Modbus-RTU
    Baud Rate 1200–38400bps
    Relay Contact AC 250V/3A, DC 30V/3A
    Pulse Constant 10000 imp/kWh, settable
    Analog Output 4–20mA, optional
    Auxiliary Power AC/DC 85–265V
    Operating Temperature -25°C to +65°C
    Storage Temperature -40°C to +80°C
    Humidity ≤93%RH, non-condensing
    Altitude ≤2500m
    Function AMC96L-E4/KC
    Three-phase Voltage
    Zero-sequence Voltage
    Three-phase Current
    Zero-sequence Current
    Three-phase Active Power
    Total Active Power
    Three-phase Reactive Power
    Total Reactive Power
    Three-phase Apparent Power
    Total Apparent Power
    Three-phase Power Factor
    Total Power Factor
    Frequency
    Voltage Phase Angle
    Voltage Unbalance
    Current Unbalance
    Forward / Reverse Power
    Four-quadrant Energy Metering
    System Time Display
    RS485
    Modbus-RTU
    4DI + 2DO + 1 Energy Pulse Optional
    2DI + 2DO + 1 Energy Pulse Optional
    Multi-tariff Energy Metering Optional
    2nd–31st Harmonic Measurement Optional
    2-channel Analog Output Optional
    1-channel Analog Output Optional
    2DI (AC 220V) + 2DO + 1 Energy Pulse Optional
  • Write your message here and send it to us
    -->