head_banner_pro

ADL400N-CT Three Phase MID UL Energy Meter

●Measure bidirectional voltage, current, power, forward and reverse power in AC system

●80A, 120A,200A,300A input

●RS485(MODBUS-RTU)

●Certification: CE, MID, UL, RoHS

●DIN 35 mm


Information

Parameter

Download

General

    ADL series DIN-rail mounted multifunctional electric energy meter is an intelligent instrument mainly designed for new energy power generation systems such as photovoltaic grid-connected system, micro inverter system, energy storage system, AC coupling system, etc. The product has the advantages of high precision, small volume, high respondent speed and convenient installation. The product has the features of sampling, metering and monitoring power parameters, communicating with an inverter or an energy management system (EMS), realizing the functions of preventing reverse flow, regulating power generation, charging and discharging batteries according to real-time power and accumulated electric energy, and realizing bidirectional metering and household distributed photovoltaic energy management.

Function

√ Input voltage
    3×230/400V, 3×277/480V

√ Input current
     80A, 120A, 200A, 300A

√ Response rate
     ≤100ms

XSX06081
XSX06086
√ Installation
      35mm Din-rail method
 
√ Dimension(L*W*H)
      90*45*65mm

Wiring

123

Three-phase Four-wire Connection Through Current Transformer

1234

Three-phase Three-wire Connection Through Current Transformer

Structure

1741326840051

Related Products

DTSD1352-C

Three-phase solar energy meter

ACR10R-DxxTE

Single-phase solar energy meter

ADL200N-CT

Single-phase solar energy meter

ADL400N-CT is a three-phase four-wire DIN-rail energy meter for photovoltaic, storage and distribution monitoring. Current comes from an external split-core coil, so the live conductor is not cut, and the meter can be programmed from its keys over RS485.

  • Rated voltage

    AC 3 x 230/400 V

  • Current input

    0.5-10(80) A / 0.5-10(120) A

  • Active energy

    Class B

  • Response

    100 ms or less

Technical data

Parameter Value (from the product manual)
GridThree-phase four-wire, forward and reverse metering
Rated voltageAC 3 x 230/400 V, input range +/-20%
Voltage overload1.2 x rated continuous; 2 x rated for 1 s; 2 W and 10 VA or less
Input currentAC 0.5-10(80) A or AC 0.5-10(120) A through the split-core coil
Current overload1.2 x rated continuous; 2 x rated for 1 s; 1 W and 1 VA or less
Measurement accuracyVoltage, current, power and frequency within +/-0.5%
Frequency50 / 60 Hz, within +/-0.5%
Active energyClass B; reactive energy Class 2 accuracy
Response rate100 ms or less for voltage, current and power; 1 s or less for energy
SafetyMeasurement category CAT III, overvoltage class OVC III
Withstand voltageAC 3 kV / 1 min between communication and signal input
Insulation resistanceInput and output terminals to casing over 100 MOhm
Power consumption2 W or less
EMCClass E2
CommunicationRS485, Modbus-RTU, address and ratio programmable from the keys
DisplaySegmented LCD with LED operation indication
Pulse outputActive energy pulse

Measured functions

Function ADL400N-CT
Electric energyActive and reactive energy, forward and reverse; split-phase energy
Electric quantityU, I, P, Q, S, PF, frequency
ProgrammingKeys set communication address, transformation ratio and other parameters
DisplaySegmented LCD
CommunicationRS485, Modbus-RTU

Built-in functions

  • Bidirectional active and reactive energy for PV and storage circuits
  • Split-phase energy for load balancing on the three phases
  • Coil current input means no need to cut or unbolt the live conductor
  • Compact rail body fits inside distribution cabinets and inverter enclosures

Before you request a quote

  • Maximum load current (80 A or 120 A coil)
  • Conductor or busbar size at the mounting point
  • Metering direction and protocol your system expects

Tell us the conductor size, the maximum load current and your inverter or EMS protocol, and we confirm the coil range, the wiring diagram and the Modbus register list within one working day.


  • Previous:
  • Next:

  • 1.Technical parameter

    Item Performance Parameters
    Model Series ADL200N-CT ADL400N-CT
    Measurement Grid Single-phase Three-phase four-wire, three-phase three-wire, single-phase three-wire
    Voltage Rated voltage 230V Three-phase: 3×220/380V, 3×230/400V, 3×277/480V 
    Input Range ±20%
    Overload 1.2 times rating (continuous)2 times the rating for 1 second
    Power consumption <0.2VA
    Accuracy class Error ±0.5%
    Current Input current 80A, 120A, 200A, 300A 3×80A, 3×120A, 3×200A, 3×300A
    Overload 1.2 times rating (continuous)2 times the rating for 1 second
    Power consumption <0.2VA
    Accuracy class Error ±0.5%
    Power Active, reactive, apparent power, error ±0.5%
    Grid frequency 45~65Hz, error ±0.5%
    Response rate ≤100ms (voltage, current, power)
    ≤1s (electrical energy)
    Metering Electric energy Active energy : Class B (split current transformer)Reactive energy (Class 2 accuracy)
    Electromagnetic Compatibility Electrostatic discharge immunity class III
    Electrical fast transient burst immunity class IV
    Surge (shock) immunity Class IV
    Security Power frequency withstand voltage Between communication and signal input, AC4kV 1min
    Insulation resistance Input and output terminals to casing >100MΩ
    Communication Interface and communication protocol RS485 interface and Modbus RTU protocol
    Communication address range Modbus RTU: 1~ 247;
    Baud rate Support 1200bps-38400bps
    Environment Operating temperature -40℃~+70℃
    Storage temperature -40℃~+70℃
    Relative humidity ≤95% (without condensation)
    Altitude ≤3000m
    Write your message here and send it to us
    -->