head_banner_pro

ADL400M Three-Phase Energy Meter

Application:

(1) PV systems
(2) Energy storage systems
(3) Microinverter systems
(4) AC-coupled systems

Basic Parameters:

(1) Three-phase four-wire, 3×230/400V
(2) External CT input
(3) Max. current: 80A / 120A / 200A / 300A
(4) RS485, Modbus RTU
(5) Bidirectional energy metering


Information

Parameter

Function

Download

Characteristic

5

Dual-Circuit Three-Phase Metering
Dual-Circuit Energy Metering
Three-Phase Four-Wire
Forward & Reverse Energy Metering

6

Compact 1P Design
Only 18mm Wide
1P DIN-Rail Design
Compact and Space-Saving

7

Fast Response
Power Response Time: 50ms
Real-Time Power Monitoring
Suitable for Inverter & EMS Control

General

ADL400M is a three-phase energy meter with external CTs, designed for PV, energy storage, microinverter and AC-coupled systems. It supports bidirectional energy metering, electrical parameter monitoring and RS485 Modbus RTU communication.

Function

Connection

Three-Phase Four-Wire

Voltage

Nominal Voltage: 3×230/400V
Input Range: 0.8Unom–1.2Unom

Current

External CT Input
D10: 80A
D16: 120A
D24: 200A
D36: 300A

Accuracy

Voltage: ±0.5%
Current: ±0.5%
Power: ±1%
Active Energy: Class 1 or B
Frequency: ±0.5%

Energy Metering

Forward and Reverse Active Energy
Forward and Reverse Reactive Energy
Split-Phase Energy
Bidirectional Energy Metering

DSC01000_clipped_rev_1
DSC01015_clipped_rev_1

Communication

RS485, Modbus RTU
Address: 1–247
Baud Rate: 1200–38400bps

Response Rate

50ms (Power)

Environment

Operating Temperature: -25℃ to +55℃
Extreme Operating Temperature: -40℃ to +70℃
Storage Temperature: -40℃ to +85℃
Relative Humidity: ≤95%, Non-condensing
Altitude: ≤2000m

Protection

Installation Category: CAT III
Overvoltage Category: OVC III
Front: IP51
Overall: IP20
Protection Class: Class II
Pollution Degree: II

Safety

Power Frequency Withstand Voltage: AC 3kV / 1min
Insulation Resistance: >100MΩ

Wiring

adl200m_wiring

Installation

adl200m_installation

Typical connection

8

  • Previous:
  • Next:

  • Item Parameter
    Grid Three-phase four-wire
    Nominal Voltage 3×230/400V
    Voltage Range 0.8Unom–1.2Unom
    Voltage Accuracy ±0.5%
    Minimum Current 0.3A
    Transitional Current 1.5A
    Basic Current 30A
    Maximum Current D10: 80A; D16: 120A; D24: 200A; D36: 300A
    Current Accuracy ±0.5%
    Power Accuracy ±1%
    Frequency 50Hz
    Frequency Accuracy ±0.5%
    Response Rate 50ms (Power)
    Active Energy Accuracy Class 1 or B
    Communication RS485
    Protocol Modbus RTU
    Communication Address 1–247
    Baud Rate 1200–38400bps
    Operating Temperature -25℃ to +55℃
    Storage Temperature -40℃ to +85℃
    Relative Humidity ≤95%, Non-condensing
    Altitude ≤2000m
    IP Rating Front: IP51; Overall: IP20
    Function Description
    Active Energy Metering Forward and reverse active energy
    Reactive Energy Metering Forward and reverse reactive energy
    Split-Phase Energy Supports split-phase energy metering
    Electrical Measurement U, I, P, Q, S, PF, F
    Communication RS485, Modbus RTU
  • Write your message here and send it to us
    -->