Multi-Circuit DC Metering
30 or 48 DC Branch Circuits
Independent Branch Energy Metering
Comprehensive Monitoring
Voltage, Current, Power & Energy
Branch Switch Status Monitoring
Hall Sensor & Communication
5V Hall Sensor Input
RS485 (Modbus-RTU)
DC Voltage Measurement: DC Bus Voltage Measurement
Current Measurement: 30 or 48 DC Branch Current Measurements
Power Measurement: Individual Branch Power Measurement
Energy Metering: Individual Branch Energy Measurement
Multi-Circuit Metering:
AMC100-FDK30: 30 DC Branch Circuits
AMC100-FDK48: 48 DC Branch Circuits
Switch Status Monitoring: Active Contact Status Monitoring for Each Branch
Hall Sensor Input: 5V Input with External Hall Sensors
Current Ratio Setting: Hall Sensor Ratio Configurable via Touch Screen
Communication: RS485 (Modbus-RTU)
Installation: 35mm DIN Rail or Base-Plate Mounted
Models: AMC100-FDK30 / AMC100-FDK48
Rated Bus Voltage: 48V DC / 240V DC / 336V DC
Voltage Measurement Range: ±20% of Rated Voltage
Current Input: 5V DC
(External Hall Sensor Required)
Default Primary Current: 100A
(Configurable According to Hall Sensor Ratio)
Voltage Accuracy: Class 0.5
Current Accuracy: Class 0.5
Power Accuracy: Class 1
Energy Accuracy: Class 1
Auxiliary Power Supply: Powered by AMC100-ZD
or DC 12–24V When Used Independently
Communication: RS485 (Modbus-RTU)
Working Temperature: -15°C to +55°C
Storage Temperature: -25°C to +70°C
Humidity: ≤93% RH
Altitude: ≤2500m
Protection Level: IP20
Installation: 35mm DIN Rail or Base-Plate Mounted