head_banner_pro

AMC16-DETT 6-Channel DC Energy Meter

Application:

Purpose-built for -48 VDC telecom sites where tower, shelter or base-station infrastructure is shared by multiple operators. Six-channel submetering helps allocate energy use by tenant or load group.
Basic Parameters: AMC16-DETT measures six DC circuits using 5 V-secondary Hall sensors and operates from a -40 to -60 VDC auxiliary supply. It provides RS485 communication, a ±12 V Hall-sensor supply output and 35 mm DIN-rail installation. AMC16L-DETT is the separate LCD version.

 

Application:

Purpose-built for -48 VDC telecom sites where tower, shelter or base-station infrastructure is shared by multiple operators. Six-channel submetering helps allocate energy use by tenant or load group.
Basic Parameters: AMC16-DETT measures six DC circuits using 5 V-secondary Hall sensors and operates from a -40 to -60 VDC auxiliary supply. It provides RS485 communication, a ±12 V Hall-sensor supply output and 35 mm DIN-rail installation. AMC16L-DETT is the separate LCD version.


Information

Parameter

Download

Characteristic

5

6-Circuit DC Metering
Up to 6 DC Branch Circuits
Independent Energy Metering

6

Communication
RS485 (Modbus-RTU)
Alarm & Data Storage Functions

7

Hall Sensor Support
0–5V DC Current Input
External Hall Sensors

Main Functions

DC Voltage Measurement: Total DC Bus Voltage

DC Current Measurement: Total Output Current and 6 Branch Currents

Power Measurement: Total Power and Individual Branch Power

Energy Metering: Total Energy and Individual Branch Energy

Multi-Circuit Metering: Up to 6 DC Branch Circuits

Hall Sensor Input: 6 Channels, 0–5V DC Input with External Hall Sensors

Hall Sensor Power Supply: +12V/100mA, -12V/50mA

Communication: RS485 (Modbus-RTU)

Time Synchronization: Supports Remote Time Synchronization via RS485

Alarm: DC Overvoltage / Undervoltage, Power Failure, Voltage Loss, Branch Metering Error and Internal Fault Alarm

Data Storage: Historical Energy Data and Alarm Information

Installation: Standard 35mm DIN Rail

Main Parameters

Rated Voltage: -48V DC

Current Input: 6 Channels, 0–5V DC
(External Hall Sensor, xxxA/5V)

Analog Input: 1 Channel, 0–5V DC

Accuracy: ±0.5%
(Excluding Hall Sensor)

Measurement Resolution:
Voltage: 0.01V
Current: 0.01A
Power: 0.01kW
Energy: 0.01kWh

01_AMC16-DETT_Product

Communication: RS485 (Modbus-RTU)

Baud Rate: 1200 / 2400 / 4800 / 9600 bps

Power Consumption: ≤2W
(Without Hall Sensor Power Output)

Working Temperature: -20°C to +60°C

Storage Temperature: -40°C to +70°C

Humidity: ≤98% RH, No Condensation

Altitude: ≤4000m

Installation: Standard 35mm DIN Rail

Dimension

01_AMC16-DETT_Dimensions

Wiring

02_AMC16-DETT_Wiring

6-Circuit DC Metering Up to 6 DC Branch Circuits Independent Energy Metering

  • Output

    RS485 (Modbus-RTU) Time Synchronization: Supports Remote Time Synchronization via RS485

    Modbus-RTU into your EMS / SCADA

  • System voltage

    -48V

  • Mounting

    Standard 35mm DIN Rail

  • Operating temp

    -20°C to +60°C

    Continuous duty

Technical data

ParameterValue
DC Voltage MeasurementTotal DC Bus Voltage DC
Current MeasurementTotal Output Current and 6 Branch Currents
Power measurementTotal Power and Individual Branch Power
Energy meteringTotal Energy and Individual Branch Energy
Multi-circuitUp to 6 DC Branch Circuits
Hall sensor input6 Channels, 0–5V DC Input with External Hall Sensors
Hall Sensor Power Supply+12V/100mA, -12V/50mA
AlarmDC Overvoltage / Undervoltage, Power Failure, Voltage Loss, Branch Metering Error and Internal Fault Alarm
Data StorageHistorical Energy Data and Alarm Information
DC Current Input6 Channels, 0–5V DC (External Hall Sensor, xxxA/5V)
Analog Input1 Channel, 0–5V DC
Accuracy±0.5% (Excluding Hall Sensor) Measurement Resolution:
Voltage0.01V
Current0.01A Power: 0.01kW Energy: 0.01kWh
Baud rate1200 / 2400 / 4800 / 9600 bps Power Consumption: ≤2W (Without Hall Sensor Power Output)
Storage temp.-40°C to +70°C
Humidity≤98% RH, No Condensation
Altitude≤4000m

Built-in functions

  • Communication RS485 (Modbus-RTU) Alarm & Data Storage Functions
  • Hall Sensor Support 0–5V DC Current Input External Hall Sensors

DIN-rail mounted. Send us the rated values of your circuit and the supply voltage; we confirm the ordering code, wiring diagram and register list within one working day.


  • Previous:
  • Next:

  • 01_DTSD1352-4S_Parameters

  • Write your message here and send it to us
    -->