APM521 3-Phase Multifunction Panel Meter

Application

• Maximum-demand monitoring aligned with TNB's 30-minute MD calculation method for three-phase power systems
• Measures and records 30-minute average active power demand, with maximum demand and occurrence time for peak-demand analysis
• Helps commercial and industrial users identify demand peaks and manage electricity demand
• Suitable for factories, industrial parks, commercial buildings, data centers, EV charging sites and switchgear systems

Basic Parameters
● Demand: three-phase current plus active, reactive and apparent power
● Demand method: sliding window; width 1/2/3/5 min; period 5-60 min
● Rated input: 66/115 V, 230/400 V, 277/480 V or 400/690 V; 1 A or 5 A
● Accuracy: voltage/current/power +/-0.2%; active energy Class D (0.2S)
● Communication: RS485 Modbus-RTU; optional Ethernet and I/O
● Size: 96 x 96 mm panel; 88 x 88 mm cut-out


Information

Parameter

Function

Download

Characteristic

5

Communication
Standard : RS485(Modbus-RTU)
Optional : Profibus(Profibus-DP), Ethernet(Modbus-TCP, HTTP, DHCP)

6

Display
LCD display U, I, P, Q, PF, kWh and other energy consumption, power measurement, harmonic conten

7

Rated U and l
Voltage: AC 100V, 110V, 400V, 690V ; Current : AC1A, 5A, support 2.5 mm 2 line access;

General

APM series power meters ofACREL are power meters that are designed accordingto IEC standards and synchronized with intemnational advanced technology.
APM series metershavefull power measurement, enery statistics, analysis of power quality and network communications and other functions, are mainly used for comprehensive monitoring of the quality of power supply network.

Function

● Voltage, current and power accuracy: +/-0.2%
● Active energy: Class D (0.2S); reactive energy: Class 2
● Power quality: harmonics 2-63, imbalance, deviation and sequence components
● RS485 Modbus-RTU; optional Ethernet Modbus-TCP/FTP
● Optional 4DI/2DO, 2AO 4-20 mA and second RS485

96
APM521_Rail_Mounted_Installation_Full_EN

● Operating temperature: -40°C to +70°C
● Storage temperature: -40°C to +80°C
● Humidity: <=95% without condensation
● Altitude: <=2000 m
● IP54 front panel; IP30 body; indoor dry location

Appearance

01_APM521_Product_Feature_Image_Only

Wiring

01_APM521_Typical_Wiring_EN

Installation

APM521_Embedded_Installation_Full_EN
APM521_Rail_Mounted_Installation_Full_EN

Typical connection

8

Communication Standard : RS485(Modbus-RTU) Optional : Profibus(Profibus-DP), Ethernet(Modbus-TCP, HTTP, DHCP)

    Technical data

    ParameterValue
    VoltageAC 100V, 110V, 400V, 690V ; Current : AC1A, 5A, support 2.5 mm 2 line access
    Storage temperature-40°C to +80°C Humidity: <=95% without condensation Altitude: <=2000 m IP54 front panel; IP30 body; indoor dry location

    Built-in functions

    • Display LCD display U, I, P, Q, PF, kWh and other energy consumption, power measurement, harmonic conten
    • Voltage, current and power accuracy: +/-0.2%
    • Active energy: Class D (0.2S); reactive energy: Class 2
    • Power quality: harmonics 2-63, imbalance, deviation and sequence components

    Ask us about this model. Send us the rated values of your circuit and the supply voltage; we confirm the ordering code, wiring diagram and register list within one working day.


  • Previous:
  • Next:

  • Rated voltage (UL/CE) 66 V L-N / 115 V L-L; 230 V L-N / 400 V L-L; 277 V L-N / 480 V L-L; 400 V L-N / 690 V L-L
    Rated current 1 A or 5 A secondary
    Measurement accuracy Voltage and current +/-0.2%; active, reactive and apparent power +/-0.2%
    Energy accuracy Active energy Class D (0.2S); reactive energy Class 2
    Grid frequency 50 / 60 Hz, error +/-0.2%
    Response rate 200 ms or less for voltage, current and power; 1 s or less for energy
    Power quality Unbalance, phase angle, total / odd / even harmonics, 2nd-63rd content, waveform, sequence components, K-factor
    Energy functions Four-quadrant, split-phase, apparent, multi-rate and frozen energy
    Demand Real-time and maximum current, active, reactive and apparent demand with time stamp
    Event records Up to 128 DI/DO records and 128 alarm records
    Communication RS485 Modbus-RTU, address 1-247, baud 1200-38400 bps; DL/T 645-2007
    Optional communication Ethernet Modbus-TCP and FTP (E module), timed logging to MicroSD
    Optional I/O 4 DI + 2 DO, 2 analog outputs 4-20 mA, second RS485
    Auxiliary power AC/DC 85-300 V; 4 W and 10 VA or less
    Protection degree IP54 front panel, IP30 body; pollution degree class 2, OVC III
    Panel size 96 x 96 mm, cut-out 88 x 88 mm
    Shell size 86.5 x 86.5 x 50 mm; module 86 x 86 x 30.5 mm; rail version 96 x 96 x 96 mm
    Reference standards IEC 61010-1, IEC EN 61010-2-30, UL 61010-1 / 61010-2-030, GB/T 17215.321-2021, GB/T 17215.323-2022
    Operating temperature -40 ~ +70 ℃
    Storage temperature -40 ~ +80 ℃
    Relative humidity ≤ 95 %, no condensation
    Altitude ≤ 2000 m
    Installation location Indoor, dry location; pollution degree 2; overvoltage category III

    03_APM521_Function_Basic_Function_EN04_APM521_Function_Optional_Function_EN