head_banner_pro

AMC96L-E4/KCM Multi-Function Power Meter

Application:

(1)Low-voltage distribution cabinets and switchgear
(2)Industrial power monitoring and energy management systems
(3)Commercial buildings and public facilities
(4)SCADA and DCS power monitoring systems

Basic Parameters:

(1)System: 3-Phase 4-Wire
(2)Display: LCD Display
(3)Rated Voltage: AC 380V
(4)Rated Current: AC 5A
(5)Digital Input: 2DI
(6)Digital Output: 2DO
(7)Analog Output: 1 Channel, DC 4-20mA
(8)Communication: RS485
(9)Protocol: Modbus-RTU
(10)Auxiliary Power: AC/DC 85-265V
(11)Installation: Panel Mounted


Information

Parameter

Function

Download

Characteristic

5

Communication

RS485 Communication
Modbus-RTU Protocol
Baud Rate: 1200–38400bps

6

Display
LCD Display
System Time Display
Parameter Setting and Control via Keys

7

Rated U and l
Three-phase Four-wire
Rated Voltage: AC 3×57.7V/100V, AC 3×220V/380V, AC 3×380V/660V
Rated Current: AC 1A or 5A
Frequency: 45–65Hz
Voltage Overload: 1.2× continuous, 2× for 1s
Current Overload: 1.2× continuous, 10× for 1s

General

AMC96L-E4/KC is a 96-size panel-mounted multifunction power meter designed for electrical parameter measurement, energy metering and power monitoring in three-phase four-wire systems.It measures three-phase voltage and current, zero-sequence voltage and current, active, reactive and apparent power, power factor, frequency, voltage phase angle, voltage/current unbalance, forward and reverse power and four-quadrant energy.

Function

Connection
3-Phase 4-Wire

Frequency
45-65Hz

Voltage
Rated Input: AC 3×57.7V/100V, 3×220V/380V, 3×380V/660V

Current
Rated Input: AC 1A or 5A

Accuracy
Voltage: Class 0.2
Current: Class 0.2
Active Power: Class 0.5
Active Energy: Class 0.5
Reactive Power: Class 1.0
Reactive Energy: Class 1.0
Frequency: ±0.05Hz

HG9A9446
HG9A9685

Communication
1× RS485, Modbus-RTU, Baud Rate 1200-38400bps

Digital Input
2DI, Dry Contact Input

Digital Output
2DO, Relay Normally Open Contact

Relay Capacity
AC 250V/3A, DC 30V/3A

Analog Output
1 Channel, DC 4-20mA

Energy Pulse Output
10000 imp/kWh

Auxiliary Power
AC/DC 85-265V

Environment
Operating Temperature: -25℃ to +65℃
Storage Temperature: -40℃ to +80℃
Relative Humidity: ≤93%RH, Non-condensing
Altitude: ≤2500m

Wiring

amc96_wiring

Installation

amc96_installation

Typical connection

8

  • Previous:
  • Next:

  • Parameter Specification
    System 3-Phase 4-Wire
    Frequency 45-65Hz
    Rated Voltage AC 3×57.7V/100V, 3×220V/380V, 3×380V/660V
    Voltage Overload 1.2× rated continuously; 2× rated for 1s
    Voltage Power Consumption <0.5VA per circuit
    Rated Current AC 1A or 5A
    Current Overload 1.2× rated continuously; 10× rated for 1s
    Current Power Consumption <0.5VA per circuit
    Voltage Accuracy Class 0.2
    Current Accuracy Class 0.2
    Active Power Accuracy Class 0.5
    Reactive Power Accuracy Class 1.0
    Active Energy Accuracy Class 0.5
    Reactive Energy Accuracy Class 1.0
    Frequency Accuracy ±0.05Hz
    Digital Input 2DI, dry contact input
    Digital Output 2DO, relay normally open contact
    Relay Capacity AC 250V/3A, DC 30V/3A
    Analog Output 1 channel, DC 4-20mA
    Communication RS485
    Protocol Modbus-RTU
    Baud Rate 1200-38400bps
    Auxiliary Power AC/DC 85-265V
    Power Consumption ≤10VA
    Operating Temperature -25°C to +65°C
    Storage Temperature -40°C to +80°C
    Relative Humidity ≤93%RH, non-condensing
    Altitude ≤2500m
    Function Description
    Voltage Measurement Three-phase voltage, zero-sequence voltage
    Current Measurement Three-phase current, zero-sequence current
    Power Measurement Active power, reactive power, apparent power
    Power Factor Three-phase power factor and total power factor
    Frequency Frequency measurement
    Phase Angle Voltage phase angle measurement
    Unbalance Voltage and current unbalance measurement
    Energy Metering Forward and reverse, four-quadrant energy metering
    Digital Input 2DI
    Digital Output 2DO relay output
    Analog Output 1-channel DC 4-20mA
    Communication 1× RS485
    Protocol Modbus-RTU
    Display LCD display
    System Time System time display