head_banner_pro

PZ96-E3 Three-Phase Multi-Function Power Meter

PZ96-E3 is a 96×96 mm panel-mounted three-phase multi-function power meter with LED display. It measures voltage, current, active/reactive/apparent power, power factor, frequency and four-quadrant energy. Optional RS485 Modbus-RTU communication, DI/DO, pulse output, analog output, event recording and harmonic measurement are available.


Information

Parameter

Function

Download

General

PZ96-E3 is a 96-square panel-mounted three-phase three-wire Multi-Function Power Meter. It measures three-phase voltage, current, active power, reactive power, power factor, frequency, active energy and reactive energy. With optional RS485 communication using Modbus-RTU, the meter can be integrated into power monitoring, SCADA and energy management systems.

Specification

03_PZ96-E3_dimensions_and_cutout

Function

Designed for three-phase three-wire systems. Measures current, voltage, active and reactive power, power factor, frequency, active energy and reactive energy. Rated voltage: AC 100 V or 400 V; current input: 1 A or 5 A from external CTs; frequency: 45–65 Hz.

01_PZ96-E3_measurement
02_panel_installation

96 × 96 mm front panel, 88 × 88 mm cutout and 92 mm depth. LED display. Optional RS485 Modbus-RTU, DI/DO and analog outputs are available according to the selected suffix. Auxiliary supply: AC 85–265 V or DC 100–350 V.

Wiring

01_3P3W_2CT_and_2PT_2CT_wiring

Structure

01_PZ96-E3_system_structure

  • Previous:
  • Next:

  • Parameter PZ96-E3
    Product Type Three-Phase Multi-Function Power Meter
    Installation Panel Mounted
    Display LED
    Wiring 3-phase 3-wire / 3-phase 4-wire
    Current Input AC 1A / 5A
    Voltage Input 100V / 400V class
    660V Input Available for applicable 96-size configuration
    Frequency 45–65Hz
    Voltage Accuracy Class 0.2
    Current Accuracy Class 0.2
    Active Power Accuracy Class 0.5
    Active Energy Accuracy Class 0.5
    Reactive Power Accuracy Class 1.0
    Frequency Accuracy 0.05Hz
    Communication Optional RS485 / Modbus-RTU
    Analog Output Optional 1–5V / 4–20mA
    Auxiliary Power Supply AC/DC 85–265V
    Operating Temperature -10°C to +55°C
    Panel Size 96 × 96 mm
    Cut-out Size 88 × 88 mm
    Installation Depth 77.8 mm
    Altitude ≤2500m
    Function PZ96-E3
    Three-Phase Voltage Standard
    Three-Phase Current Standard
    Active Power Standard
    Reactive Power Standard
    Apparent Power Standard
    Power Factor Standard
    Frequency Standard
    Four-Quadrant Energy Standard
    LED Display Standard
    RS485 Modbus-RTU Optional
    DI / DO Optional
    Energy Pulse Output Optional
    Analog Output Optional
    Event Recording (SOE) Optional
    Maximum Demand With SOE option
    Harmonic Measurement Optional, 2nd–31st
    Second Communication Port Optional