AMC100-FAK AC Multi-Circuit Power Meter

Application:

Designed for high-density AC outgoing-feeder monitoring in data center precision distribution cabinets, column-head cabinets and intelligent PDUs. One module centralizes electrical measurements for the A and B power paths.
Basic Parameters:

AMC100-FAK30 and AMC100-FAK48 monitor 30 or 48 AC outgoing circuits in total. The module is designed for a 220 VAC bus, matched 50 mA-secondary current transformers, RS485 Modbus-RTU communication and 35 mm DIN-rail or base-plate mounting.


Information

Parameter

Download

Characteristic

5

ulti-Circuit AC Metering
30 or 48 Single-Phase Circuits
Up to 10 or 16 Three-Phase Circuits

6

Comprehensive Monitoring
Voltage, Current, Power, Energy & Harmonics
Independent Branch Monitoring

7

Switch Status & Communication
Branch Switch Status Monitoring
RS485 (Modbus-RTU)

Main Functions

05_AMC100-FAK_Detail

Voltage Measurement: AC Branch Voltage Measurement

Current Measurement: 30 or 48 AC Branch Current Measurements

Power Measurement: Active Power & Reactive Power

Power Factor: Power Factor Measurement

Frequency: AC Frequency Measurement

Energy Metering: Active Energy & Reactive Energy

Multi-Circuit Metering:
AMC100-FAK30: 30 Single-Phase / 10 Three-Phase Circuits
AMC100-FAK48: 48 Single-Phase / 16 Three-Phase Circuits

Harmonics: 2nd–31st Current Harmonic Measurement

Switch Status Monitoring: Branch Switch Status Monitoring

Current Input: External CT, Secondary 50mA

Communication: RS485 (Modbus-RTU)

Installation: 35mm DIN Rail or Base-Plate Mounted

Main Parameters

Models: AMC100-FDK30 / AMC100-FDK48

Rated Bus Voltage: 48V DC / 240V DC / 336V DC

Voltage Measurement Range: ±20% of Rated Voltage

Current Input: 5V DC
(External Hall Sensor Required)

Default Primary Current: 100A
(Configurable According to Hall Sensor Ratio)

Voltage Accuracy: Class 0.5

Current Accuracy: Class 0.5

Power Accuracy: Class 1

Energy Accuracy: Class 1

Auxiliary Power Supply: Powered by AMC100-ZD
or DC 12–24V When Used Independently

03_AMC100-FAK_Terminals
03_AMC100-FDK_Terminals

Auxiliary Power Supply: Powered by AMC100-ZA
or DC 12–24V When Used Independently

Communication: RS485 (Modbus-RTU)

Working Temperature: -15°C to +55°C

Storage Temperature: -25°C to +70°C

Humidity: ≤93% RH

Altitude: ≤2500m

Protection Level: IP20

Installation: 35mm DIN Rail or Base-Plate Mounted

Dimension

01_AMC100-FAK_Dimensions

Wiring

02_AMC100-FAK_Wiring

  • Previous:
  • Next:

  • 01_AMC100-FAK_Parameters

  • Write your message here and send it to us
    -->