ADW2XX series rail type multiloop power instrument

● Mearsure Up to 4 circuit 3 phase

● Mearsure all electric parameters

● Split core open loop CTs

● External function module, such as MK, MTL, wireless communication


Information

Parameter

Download

5

Communication

RS485(Modbus-RTU)

6

Display

LCD Display

7

Rated U and I

3x220/380 100A, 5A

General

      ADW2XX series rail type multi-loop power meters are mainly used for measuring the full electric parameters ofmulliple three-phase circuits, Up to four three-phase loop current inputs can be connected simultaneously.It Can measurevoltage and current, power, power factor, phase angle, unbalance, harmonic and other parameters.

Characteristic

11

Accuracy
Active energy: Class 1
Reactive energy: Class 2
Frequency
Range: 45-65HZ
Pulse output
Active pulse output and Reactive pulse
output(or Clock pulse output)

Dimension(L"W"H)
72*97.7*36mm
Installation:
DIN 35mm
Starting current
4%olb(1 class)

12

Display Sample

23

Installation instructions

24
● Adw2xx installation mode is rail type; Up to 4 three-phase current connections
●Note: It is recommend that the distance between AKH-0.66/K- ∅ 10N installation postion and the primary side transformer should be more than 1 meter.

Dimension Of Transformer

 

Current Transformer

Dimension(mm) Perforation size (mm)  

tolerance(mm)

W H D M N Φ1 Φ2

AKH-0.66/K-。

10N 27 44 32 25 36 10 9  

 

±1

AKH-0.66/K-。

16N 31 50 36 27 42 16 17

AKH-0.66/K-。

24N 39 71 46 36 52 24 23.5

AKH-0.66/K-。

36N 42.5 82 58 40 56 33.5 35

Typical Connection

25

ADW2xx is a rail-mounted multi-loop power instrument: one unit measures up to four three-phase circuits at the same time through external open-type current transformers, so a whole distribution box can be metered by a single device.

  • Voltage input

    AC 3 x 220/380 V

  • Three-phase loops

    1 to 4 per unit

  • Current

    5 A, 100 A, 400 A, 600 A open CT

  • Harmonics

    2nd-31st, +/-1%

Technical data

Parameter Value (from the product manual)
Circuits per instrument1, 2, 3 or 4 three-phase circuits, each with its own external CT
Auxiliary powerAC/DC 85-265 V, DC 48 V or AC 380 V; 10 VA or less
Input frequency45-65 Hz
Voltage inputAC 3 x 220/380 V; 1.2 x rated continuous, 2 x rated for 1 s; 0.5 VA or less per channel
Current inputAC 5 A, 100 A, 400 A or 600 A with external open-type CT; 1.2 x continuous, 10 x for 1 s
Measurement accuracyFrequency 0.05 Hz; voltage and current class 0.5; active energy class 1; reactive energy class 2
Harmonic measurement2nd-31st order within +/-1%
Current transformerAKH-0.66/K series round perforation, class 0.5 (class 1 for the L-45 type)
Pulse outputOptocoupler pulse with open collector, output can be switched to the corresponding circuit
CommunicationRS485, Modbus-RTU, baud 1200-38400 bps
Switching input / output2 DI + 2 DO standard; expansion module with 12 DI + 4 DO
Temperature and leakage12 external NTC temperature channels + 4 residual current measurements
Switch output ratingRelay normally open contact, AC 250 V / 3 A, DC 30 V / 3 A
Withstand voltageAC 2 kV / 1 min
Insulation resistanceOver 100 MOhm
EMCBetter than grade 3
EnvironmentWorking -20 to +60 C, storage -40 to +70 C, RH 95% or less non-condensing

Model and CT matching

Voltage Instrument Current Matching CT
3 x 220/380 VADW2xx-D10-NS(5A)3 x 5 AAKH-0.66/K 10N class 0.5
3 x 220/380 VADW2xx-D16-NS(100A)3 x 100 AAKH-0.66/K 16N class 0.5
3 x 220/380 VADW2xx-D24-NS(400A)3 x 400 AAKH-0.66/K 24N class 0.5
3 x 220/380 VADW2xx-D36-NS(600A)3 x 600 AAKH-0.66/K 36N class 0.5
-ADW200-MTL-AKH-0.66-L-45 class 1

Built-in functions

  • Several outgoing circuits metered by one instrument against one voltage reference
  • Open-type CTs clamp over the cable, so the busbar or cable does not have to be removed
  • Energy, power, demand and harmonic data per loop for sub-building sub-metering
  • Dry-contact inputs for breaker status, relay outputs for alarm or load control

Before you request a quote

  • Number of current loops to meter
  • Cable diameter or busbar cross-section through the CT window
  • Maximum current per loop

Send the number of circuits, the cable or busbar size and the maximum current per loop; we confirm the instrument type and the matching CT perforation size within one working day.