AMC100-FAK AC Multi-Circuit Power Meter

Application:

Designed for high-density AC outgoing-feeder monitoring in data center precision distribution cabinets, column-head cabinets and intelligent PDUs. One module centralizes electrical measurements for the A and B power paths.
Basic Parameters:

AMC100-FAK30 and AMC100-FAK48 monitor 30 or 48 AC outgoing circuits in total. The module is designed for a 220 VAC bus, matched 50 mA-secondary current transformers, RS485 Modbus-RTU communication and 35 mm DIN-rail or base-plate mounting.


Information

Parameter

Download

Characteristic

AMC100-FAK Characteristic

ulti-Circuit AC Metering
30 or 48 Single-Phase Circuits
Up to 10 or 16 Three-Phase Circuits

AMC100-FAK Characteristic

Comprehensive Monitoring
Voltage, Current, Power, Energy & Harmonics
Independent Branch Monitoring

AMC100-FAK Characteristic

Switch Status & Communication
Branch Switch Status Monitoring
RS485 (Modbus-RTU)

Main Functions

05_AMC100-FAK_Detail

Voltage Measurement: AC Branch Voltage Measurement

Current Measurement: 30 or 48 AC Branch Current Measurements

Power Measurement: Active Power & Reactive Power

Power Factor: Power Factor Measurement

Frequency: AC Frequency Measurement

Energy Metering: Active Energy & Reactive Energy

Multi-Circuit Metering:
AMC100-FAK30: 30 Single-Phase / 10 Three-Phase Circuits
AMC100-FAK48: 48 Single-Phase / 16 Three-Phase Circuits

Harmonics: 2nd–31st Current Harmonic Measurement

Switch Status Monitoring: Branch Switch Status Monitoring

Current Input: External CT, Secondary 50mA

Communication: RS485 (Modbus-RTU)

Installation: 35mm DIN Rail or Base-Plate Mounted

Main Parameters

Models: AMC100-FDK30 / AMC100-FDK48

Rated Bus Voltage: 48V DC / 240V DC / 336V DC

Voltage Measurement Range: ±20% of Rated Voltage

Current Input: 5V DC
(External Hall Sensor Required)

Default Primary Current: 100A
(Configurable According to Hall Sensor Ratio)

Voltage Accuracy: Class 0.5

Current Accuracy: Class 0.5

Power Accuracy: Class 1

Energy Accuracy: Class 1

Auxiliary Power Supply: Powered by AMC100-ZD
or DC 12–24V When Used Independently

03_AMC100-FAK_Terminals
03_AMC100-FDK_Terminals

Auxiliary Power Supply: Powered by AMC100-ZA
or DC 12–24V When Used Independently

Communication: RS485 (Modbus-RTU)

Working Temperature: -15°C to +55°C

Storage Temperature: -25°C to +70°C

Humidity: ≤93% RH

Altitude: ≤2500m

Protection Level: IP20

Installation: 35mm DIN Rail or Base-Plate Mounted

Dimension

01_AMC100-FAK_Dimensions

Wiring

02_AMC100-FAK_Wiring

ulti-Circuit AC Metering 30 or 48 Single-Phase Circuits Up to 10 or 16 Three-Phase Circuits

  • Output

    RS485 (Modbus-RTU)

    Modbus-RTU into your EMS / SCADA

  • System voltage

    48V DC / 240V DC / 336V DC

  • Voltage range

    ±20% of Rated Voltage

  • Voltage accuracy

    Class 0.5

Technical data

ParameterValue
Voltage MeasurementAC Branch Voltage Measurement
Current Measurement30 or 48 AC Branch Current Measurements
Power measurementActive Power & Reactive Power
Power FactorPower Factor Measurement
FrequencyAC Frequency Measurement
Energy meteringActive Energy & Reactive Energy
Multi-circuitAMC100-FAK30: 30 Single-Phase / 10 Three-Phase Circuits AMC100-FAK48: 48 Single-Phase / 16 Three-Phase Circuits
Harmonics2nd–31st Current Harmonic Measurement
Switch statusBranch Switch Status Monitoring
Current inputExternal CT, Secondary 50mA
Installation35mm DIN Rail or Base-Plate Mounted
ModelsAMC100-FDK30 / AMC100-FDK48
Default primary current100A (Configurable According to Hall Sensor Ratio)
Current accuracyClass 0.5
Power accuracyClass 1
Energy accuracyClass 1
Auxiliary powerPowered by AMC100-ZD or DC 12–24V When Used Independently
Working temp.-15°C to +55°C
Storage temp.-25°C to +70°C
Humidity≤93% RH
Altitude≤2500m
ProtectionIP20

Built-in functions

  • Comprehensive Monitoring Voltage, Current, Power, Energy & Harmonics Independent Branch Monitoring
  • Switch Status & Communication Branch Switch Status Monitoring RS485 (Modbus-RTU)

DIN-rail mounted. Send us the rated values of your circuit and the supply voltage; we confirm the ordering code, wiring diagram and register list within one working day.


  • Previous:
  • Next:

  • Instrument model AMC100-FAK30 / AMC100-FAK48
    Measurement parameters Voltage, current, frequency, active power, reactive power, power factor, active energy, reactive energy, 2nd-31st total current harmonic content
    Bus voltage Rated 220 VAC; measuring range ±20 %; overload instantaneous voltage 2 times / s
    Current outlet loop Rated 50 mA; range 0.125-60 mA; overload continuous 1.2 times, instantaneous 10 times / s
    Input frequency AC 45-65 Hz
    Measurement accuracy Voltage / current / active power / active energy Class 0.5; reactive power / reactive energy Class 1
    Auxiliary power Powered by AMC100-ZA; DC 12-24 V supply when used alone
    Operating temperature -15 to +55 °C
    Storage temperature -25 to +70 °C
    Relative humidity ≤ 93 %
    Altitude ≤ 2500 m
    Communication RS485 / Modbus-RTU
    Installation method 35 mm DIN rail or bottom-plate installation
    Protection degree IP20
    Pollution degree 2
    Insulation Insulation resistance between all terminals and the conductive shell parts ≥ 100 MΩ
    Withstand voltage AC 2 kV / 1 min between voltage and current circuits of circuits A and B and other ports; leakage current < 2 mA, no breakdown or flashover
    Electrostatic discharge Level 4
    Radiated RF electromagnetic field Level 3