ob_start_detected

Key Parameters Essential specifications for quick product selection SYSTEM & POWER Up to 380V Low-voltage application Auxiliary power: AC/DC 85–265V CURRENT INPUT 1A / 5A CT secondary input Ia / Ib / Ic / In current channels COMMUNICATION RS485 Standard communication interface Protocol: Modbus-RTU COMPACT SIZE 96 × 96mm Front size: 96 × 96mm Cutout: 88 × 88mm Housing: 90 × 90 × 46mm RELAY OUTPUT 2 × SPDT.
| Parameter | Value |
|---|---|
| Protocol | Modbus-RTU COMPACT SIZE 96 × 96mm |
| Front size | 96 × 96mm |
| Cutout | 88 × 88mm |
| Housing | 90 × 90 × 46mm RELAY OUTPUT 2 × SPDT Dual-channel relay output AC 250V / 5A DC 30V / 5A OPTIONAL FUNCTION 30–1000mA Residual current measurement External RCT required Panel-mounted design: 88 × 88mm cutout Front IP54 Terminals IP20 Working temperature -20℃ to +70℃ |
Panel-mounted. Send us the rated values of your circuit and the supply voltage; we confirm the ordering code, wiring diagram and register list within one working day.
| Technical Parameter | Qualification | ||
|---|---|---|---|
| Accessory Power Supply | Voltage Range | AC/DC 85–265V | |
| Power Dissipation | — | ||
| Input | Current Specifications | ABCN (4-channel): 1A/5A | 10%Ie–1000%Ie, ±2% |
| Residual Current Specification | 30mA–1000mA | ±2% | |
| Frequency | 45Hz–65Hz | ±0.2Hz | |
| Output | Output Method | Dual-channel Single-pole Double-throw Switch | |
| Output Capacity | Resistive Load; AC 250V 5A / DC 30V 5A | ||
| Installation and Usage Environment | Workplace Scenario | No direct exposure to rain or snow; no corrosive gases; no severe vibration | |
| Relative Humidity | ≤95% RH, No Condensation | ||
| Working Temperature | -20℃ to +70℃ | ||
| Storage Temperature | -40℃ to +70℃ | ||
| Altitude | ≤2000m | ||
| Installation / Protection Level | Embedded Installation: 88 × 88mm | Panel: IP54; Terminals: IP20 | |
| Security Classification | EMC | Level III | |
| Function | Standard Configuration | Optional | |
|---|---|---|---|
| Measurement Function | Three-phase Alternating Current | √ | |
| Neutral Conductor Current | √ | ||
| Residual Current | √ | ||
| Protective Function | Inverse-time Overcurrent Protection | √ | |
| Inverse-time Grounding | √ | ||
| Three-stage Time-delayed Overcurrent Protection | √ | ||
| Three-stage Time-delayed Ground Fault Protection | √ | ||
| Current Imbalance | √ | ||
| Leakage Current | √ | ||
| Communication Function | Modbus-RTU | √ | |
| Digital Output Function | 2 Single-pole Double-throw Switches | √ | |
| Record Function | 20 Fault Records | √ | |
| 20 Event Records | |||
| Display Function | Liquid-crystal Display | √ | |
| Setpoint Setting Function | Operation Panel Modification | √ | |
| Communication Amendment | |||