head_banner_news

Power Factor Dropped to 0.3 After Grid-Connected PV? How ANSVG Turned Penalties into Credits?


    The factory installed solar PV to cut energy costs, but its power factor fell below 0.5 after grid connection. Power-factor adjustment charges appeared every month, and 13 of 40 capacitor units bulged and failed. After Acrel ANSVG static var generators were installed, the electricity bill changed from a penalty to a credit in just over one month.

1. The Hidden Burden Created by Solar PV

In 2026, a condiment manufacturer in Shanghai installed solar PV at its factory. The clean-energy project was intended to reduce costs, but power-quality problems quickly followed the grid connection.

Because the factory load was relatively light, not all PV generation could be consumed on site. Active power imported from the grid fell sharply, while reactive power remained high. During periods of strong sunlight, the power factor of the two 1,600 kVA transformers dropped to about 0.5 and 0.3. On-site measurements were as low as 0.37 and 0.49.

图片1

Before treatment: power factor 0.37

图片2

Before treatment: power factor 0.49

What does a power factor of 0.3 or 0.5 mean? Under the applicable Power Factor Adjustment Electricity Charge Measures, a monthly average power factor below 0.90 results in an additional adjustment charge. In this case, every 0.01 decrease added 2% to the charge. The impact was not limited to a higher monthly bill; the distribution system was also operating under persistent stress.

2. A Different Approach: ANSVG Static Var Generator

Traditional SVC capacitor banks switch capacitors mechanically. They respond slowly, provide only stepped compensation, and can amplify resonance when harmonics are present. Overheating, bulging and eventual capacitor failure become difficult to avoid.

When a conventional capacitor bank could no longer manage the post-PV condition, Acrel replaced it with an ANSVG static var generator. ANSVG injects a controlled reactive current into the grid in real time, providing stepless, bidirectional compensation with millisecond-level response.

Fast response: Response time below 5 ms enables rapid tracking of load changes and keeps the power factor above 0.95.
Wide compensation range: Continuous adjustment across inductive and capacitive conditions both supplies reactive power and absorbs surplus reactive power associated with PV operation.
Harmonic mitigation: While compensating reactive power, the system can partially suppress selected harmonic orders and help protect distribution equipment.
Flexible installation: The modular units operate independently, so a single-module fault does not stop the whole system. Installation and maintenance are straightforward and reliability is high.
Centralized monitoring: A large touchscreen displays power factor, current, harmonics and other electrical parameters, making system status easy to review.
图片3
3. Implemented Solution: Four 150 kVar ANSVG Units in Parallel
Based on the actual load profile and compensation requirement, Acrel designed a dual-unit parallel solution for each transformer. The arrangement replaced the original SVC capacitor-bank compensation.
Compensation Point System Configuration Functional Role
Point 1 - Transformer No. 1 Two 150 kVar ANSVG units in parallel Real-time linear reactive-power compensation; power factor maintained above 0.95; utility penalties avoided.
Point 2 - Transformer No. 2 Two 150 kVar ANSVG units in parallel Real-time linear reactive-power compensation; power factor maintained above 0.95; utility penalties avoided.

Configuration of the four-unit, two-transformer compensation scheme

4. Measured Results: Power Factor from 0.47 to 1.00

After commissioning, real-time measurements collected from the ANSVG touchscreen provided clear evidence of the improvement.

Measurement Before Treatment After Treatment
Device 1 0.47 - load side 1.00 - grid side, 2026-08-03 11:54
Device 2 0.60 - load side 1.00 - grid side, 2026-08-03 13:31

On-site ANSVG power-factor measurements before and after treatment

The electricity bills provide even more direct evidence. Official State Grid Shanghai bills for July 2026 show that both receiving points exceeded the 0.90 assessment standard and received a negative adjustment charge, which appears as a credit.

Receiving Point Actual Power Factor Assessment Standard Adjustment Coefficient PF Adjustment Charge
No. 1 0.97 0.90 -0.75% CNY -674.87 (credit)
No. 2 0.99 0.90 -0.75% CNY -1,063.53 (credit)

Source: State Grid Shanghai electricity bills, July 2026

5. Business Impact: From Monthly Penalties to Monthly Credits

The two receiving points generated a combined monthly power-factor adjustment credit of CNY 1,738.40. Compared with the high penalties before the retrofit, the system now reduces the electricity bill and allows the PV investment to deliver its intended savings.
Site Condiment manufacturing facility, Shanghai, China
Electrical System Two 1,600 kVA transformers
Installed Compensation Four 150 kVar ANSVG units; two units in parallel per transformer
Lowest Pre-Retrofit PF 0.37 and 0.49 in on-site measurements
Post-Retrofit PF 1.00 at the ANSVG touchscreen; 0.97 and 0.99 in the monthly bill assessment
Monthly PF Adjustment CNY 1,738.40 credit
Estimated Annual Savings Approximately CNY 21,000 from the PF adjustment item alone

Project results at a glance

5. Business Impact: From Monthly Penalties to Monthly Credits

The two receiving points generated a combined monthly power-factor adjustment credit of CNY 1,738.40. Compared with the high penalties before the retrofit, the system now reduces the electricity bill and allows the PV investment to deliver its intended savings.

Site Condiment manufacturing facility, Shanghai, China
Electrical System Two 1,600 kVA transformers
Installed Compensation Four 150 kVar ANSVG units; two units in parallel per transformer
Lowest Pre-Retrofit PF 0.37 and 0.49 in on-site measurements
Post-Retrofit PF 1.00 at the ANSVG touchscreen; 0.97 and 0.99 in the monthly bill assessment
Monthly PF Adjustment CNY 1,738.40 credit
Estimated Annual Savings Approximately CNY 21,000 from the PF adjustment item alone

Project results at a glance

Over one year, the power-factor adjustment item alone represents approximately CNY 21,000 in savings. This estimate excludes longer-term benefits from preventing capacitor bulging and failure, reducing transformer losses and lowering line losses.

The ANSVG series is supported by granted invention patents, software copyrights, utility-model patents and design patents, providing a reliable quality foundation for delivered systems.

If grid-connected PV drives power factor too low and triggers adjustment charges;
if capacitor banks bulge, resonate or fail repeatedly;
or if reactive-power compensation cannot keep pace with load fluctuations -
consider a smarter compensation method.

Acrel ANSVG - Helping Enterprises Make Better Use of Every Kilowatt-Hour


Post time: Sep-02-2026