1: The positive pole of the power supply (note that the positive pole and the negative pole of the power supply cannot be reversed) 2: Negative power supply 3: Analog output negative 4: Analog output positive
| Parameter | Value |
|---|
Ask us about this model. Send us the rated values of your circuit and the supply voltage; we confirm the ordering code, wiring diagram and register list within one working day.
| Technical parameter | Index | ||
| Accuracy class | 0.5 Class 0.5 | ||
| Input | Nominal value | BA20(Ⅱ)-AI | Current AC 0.5A, 50A, 200A, etc. AC 0~(0.5~200)A |
| BA50(Ⅱ)-AI | Current AC 60A, 300A, 600A, etc. AC 0~(60~600)A | ||
| BA50L(Ⅱ)-AI | Current AC 0.1A, 1A, etc. AC 0~(0.1~1)A | ||
| Overload | Continuous 1.2 times, instantaneous current 10 times/1S | ||
| Absorbed power | ≤1VA | ||
| Frequency response | 25Hz~800Hz, especially suitable for industrial frequency occasions | ||
| Output | Nominal value | DC4~20mA, or 0~20mA, 0~5V, 0~10V etc. | |
| Load Resistance | When DC12V power supply, current output is ≤250ΩWhen DC24V power supply, current output is ≤500Ω,When voltage output is ≥1KΩ | ||
| Communication | RS485 interface/Modbus-RTU | ||
| Response time | ≤400ms | ||
| Power supply | Voltage | DC 12V or 24V | |
| Power consumption | ≤1W | ||
| Insulation resistance | >100MΩ | ||
| Compressive strength | Between input/output and power supply 2.0KV/1min, | ||
| Temperature coefficient | -10℃~+55 ℃, ≤400ppm/℃ | ||
| Installation method | TS35 rail, or use screws to fix the | ||
| Environment | Temperature | Work: -10℃~+55℃ Storage: -25℃~+70 ℃ |
| Humidity | ≤93%RH, no condensation, no corrosive gas place | |
| Altitude | ≤2000m |