A residential community in Saudi Arabia needed centralised metering of its household circuits: every villa or apartment feeder metered, readings collected without a person walking the site with a clipboard, and the data available to the property office in real time.
The constraint that shaped the design was communication. Running a control cable back to a single collection point across a low-rise community costs more than the meters, and the trenching is disruptive after handover. The project therefore uses 4G wireless backhaul: each collection point uploads over the cellular network, and no site-wide cable bus is required.
Per-household three-phase energy metering, collected by 4G, with no manual reading.
Equipment and how it fits together
The customer selected the ADL400 three-phase DIN-rail energy meter on each monitored household circuit, paired with an AWT100-4G wireless gateway at the collection point. The meter reports over RS485 / Modbus-RTU, the gateway publishes the same registers over 4G, and the Acrel IoT power cloud platform presents consumption per household, per building and for the community as a whole.
- Real-time monitoring of voltage, current, power and energy per circuit, so an abnormal household load is visible the day it appears.
- Remote reading replaces the manual walk, and the time-stamped kWh register is what a charge to the resident is based on.
- Switchable relay control is available on the prepaid variants of the ADL series where the operator wants to disconnect on unpaid accounts.
- Visual management on one interface: consumption by region, by building and by household, with reports for the period the operator bills on.
ADL400 technical data
| Parameter | Value |
|---|---|
| System connection | Three-phase 3-wire and three-phase 4-wire |
| Reference voltage | 3×100 V, 3×380 V (3P3W) / 3×57.7/100 V, 3×220/380 V (3P4W); range up to 450 V |
| Input current | 3×1(6) A or 3×10(80) A |
| Measurement accuracy | Voltage and current ±0.2%; power ±0.5%; frequency 45–65 Hz ±0.2% |
| Energy accuracy | Active energy class 0.5; clock error ≤0.5 s/day |
| Measured quantities | U, I, P, Q, S, PF, F; positive and negative active and reactive energy; per-phase energy |
| Harmonics | 2nd to 31st voltage and current harmonics |
| Display | 12-segment LCD with 3 keys for local settings and communication |
| Pulse output | Active energy pulse, 80±20 ms; 400 imp/kWh or 10000 imp/kWh |
| Communication | RS485, Modbus-RTU, address 1–254, 1200–38400 bps |
| Burden | Voltage <10 VA per phase; current <1 VA at rated current; impedance >2 MΩ |
| Environment | Working −25 to +55 °C; ≤95% RH no condensation; ≤2500 m |
| Installation | DIN rail inside the household distribution board |
Tariff structure, maximum-demand recording and freeze functions are options on this series — tell us which of them the billing model needs before the order.