head_banner_pro

AMC72-E4 Panel-Mounted Multi-Function Power Meter

Application:

Power monitoring and energy metering in low-voltage distribution systems.

Suitable for industrial facilities, utilities, commercial buildings and intelligent buildings.

Can be integrated into SCADA and energy management systems through RS485 communication.

Basic Parameters:

Three-phase four-wire system
Rated Voltage: AC 3×57.7/100V, 3×220/380V
Rated Current: AC 1A or 5A
Frequency: 45–65Hz
Communication: RS485, Modbus-RTU
Auxiliary Power Supply: AC/DC 85–265V, DC 24V ±20% or DC 48V ±20%
Mounting: Panel-mounted


Information

Parameter

Function

Download

Characteristic

5

Communication

Interface: RS485
Protocol: Modbus-RTU
Baud Rate: 1200–38400bps

6

Display
LED Digital Display
System Time Display
Parameter Setting and Control via Keys

7

Rated U and l
Three-phase Four-wire
Rated Voltage: AC 3×57.7V/100V, AC 3×220V/380V
Rated Current: AC 1A or 5A
Frequency: 45–65Hz
Voltage Overload: 1.2× continuous, 2× for 1s
Current Overload: 1.2× continuous, 10× for 1s

General

AMC72-E4/KC is a 72-size panel-mounted multifunction power meter designed for electrical parameter measurement, energy metering and power monitoring in three-phase four-wire systems.It measures three-phase voltage and current, zero-sequence voltage and current, active, reactive and apparent power, power factor, frequency, voltage phase angle, voltage/current unbalance, forward and reverse power, and four-quadrant energy.With RS485 Modbus-RTU communication, it can be integrated into power monitoring systems, SCADA systems and energy management systems. 

Function

Connection

Three-phase four-wire

Frequency

45–65Hz

Voltage

Rated Voltage: AC 3×57.7/100V, AC 3×220/380V
Overload: 1.2 times rated value continuously; 2 times rated value for 1s
Power Consumption: <0.5VA

Current

Rated Current: AC 1A, 5A
Overload: 1.2 times rated value continuously; 10 times rated value for 1s
Power Consumption: <0.5VA

Accuracy

Voltage: Class 0.2
Current: Class 0.2
Active Power: Class 0.5
Active Energy: Class 0.5
Reactive Power: Class 1.0
Reactive Energy: Class 1.0
Frequency: ±0.05Hz
2nd–31st Harmonics: ±1%

微信图片_20260819093034_58_48
微信图片_20260819093048_59_48

Communication

Interface: RS485
Protocol: Modbus-RTU
Baud Rate: 1200–38400bps

Switching Input

Dry Contact Input
Built-in Power Supply

Switching Output

Relay Normally Open Contact
Contact Capacity: AC 250V/3A, DC 30V/3A

Analog Output

4–20mA

Auxiliary Power Supply

AC/DC 85–265V
DC 24V ±20%
DC 48V ±20%
Power Consumption: ≤10VA

Environment

Operating Temperature: -25°C to +65°C
Storage Temperature: -40°C to +80°C
Humidity: ≤93%RH, non-condensing
Altitude: ≤2500m

Wiring

amc72_wiring

Installation

amc72_installation

Typical connection

8

  • Previous:
  • Next:

  • Parameter Specification
    System 3-phase 4-wire
    Frequency 45–65 Hz
    Rated Voltage AC 3×57.7/100 V, AC 3×220/380 V
    Voltage Overload 1.2× rated value continuously; 2× rated value for 1 s
    Voltage Power Consumption <0.5 VA
    Rated Current AC 1 A or 5 A
    Current Overload 1.2× rated value continuously; 10× rated value for 1 s
    Current Power Consumption <0.5 VA
    Voltage Accuracy Class 0.2
    Current Accuracy Class 0.2
    Active Power Accuracy Class 0.5
    Reactive Power Accuracy Class 1.0
    Active Energy Accuracy Class 0.5
    Reactive Energy Accuracy Class 1.0
    Frequency Accuracy ±0.05 Hz
    Harmonic Measurement Accuracy ±1%
    Communication RS485, Modbus-RTU
    Baud Rate 1200–38400 bps
    Energy Pulse Output Open-collector optocoupler output
    Pulse Constant 10000 imp/kWh, settable
    Switching Input Dry contact input, built-in power supply
    Switching Output Relay normally open contact
    Relay Contact Capacity AC 250 V/3 A; DC 30 V/3 A
    Analog Output 4–20 mA
    Auxiliary Power Supply AC/DC 85–265 V; DC 24 V ±20%; DC 48 V ±20%
    Power Consumption ≤10 VA
    Operating Temperature -25°C to +65°C
    Storage Temperature -40°C to +80°C
    Humidity ≤93% RH, non-condensing
    Altitude ≤2500 m
    Insulation Resistance >100 MΩ
    Faceplate Size 75 × 75 mm
    Panel Cutout 67 × 67 mm
    Depth 94.3 mm

     

    Function AMC72-E4/KC
    Three-phase Voltage
    Zero-sequence Voltage
    Three-phase Current
    Zero-sequence Current
    Three-phase Active Power
    Total Active Power
    Three-phase Reactive Power
    Total Reactive Power
    Three-phase Apparent Power
    Total Apparent Power
    Three-phase Power Factor
    Total Power Factor
    Frequency
    Voltage Phase Angle
    Voltage Unbalance
    Current Unbalance
    Forward / Reverse Power
    Four-quadrant Energy Metering
    System Time Display
    RS485 Communication
    Modbus-RTU
    2DI + 2DO + 1 Energy Pulse Output (K) Optional
    4DI + 2DO (K) Optional
    Event Record (SOE) Optional
    2nd–31st Harmonic & Total Harmonic Measurement (H) Optional
    2DI + 2DO + 1 Analog Output (KM) Optional

     