Communication
Interface: RS485
Protocol: Modbus-RTU
Baud Rate: 1200–38400bps
Display
LED Digital Display
System Time Display
Parameter Setting and Control via Keys
Rated U and l
Three-phase Four-wire
Rated Voltage: AC 3×57.7V/100V, AC 3×220V/380V
Rated Current: AC 1A or 5A
Frequency: 45–65Hz
Voltage Overload: 1.2× continuous, 2× for 1s
Current Overload: 1.2× continuous, 10× for 1s
AMC72-E4/KC is a 72-size panel-mounted multi-function power meter designed for electrical parameter measurement, energy metering and power monitoring in three-phase four-wire systems.It measures three-phase voltage and current, zero-sequence voltage and current, active, reactive and apparent power, power factor, frequency, voltage phase angle, voltage/current unbalance, forward and reverse power, and four-quadrant energy.This version provides 2 digital inputs, 2 relay outputs, energy pulse output and RS485 Modbus-RTU communication, allowing status monitoring, remote control and integration with power monitoring or energy management systems.
Connection
Three-phase four-wire
Frequency
45–65Hz
Voltage
Rated Voltage: AC 3×57.7/100V, AC 3×220/380V
Overload: 1.2 times rated value continuously; 2 times rated value for 1s
Power Consumption: <0.5VA
Current
Rated Current: AC 1A, 5A
Overload: 1.2 times rated value continuously; 10 times rated value for 1s
Power Consumption: <0.5VA
Accuracy
Voltage: Class 0.2
Current: Class 0.2
Active Power: Class 0.5
Active Energy: Class 0.5
Reactive Power: Class 1.0
Reactive Energy: Class 1.0
Frequency: ±0.05Hz
2nd–31st Harmonics: ±1%
Communication
Interface: RS485
Protocol: Modbus-RTU
Baud Rate: 1200–38400bps
Switching Input
2 Digital Inputs
Dry Contact Input
Built-in Power Supply
Switching Output
2 Relay Outputs
Relay Normally Open Contact
Contact Capacity: AC 250V/3A, DC 30V/3A
Energy Pulse Output
1 Energy Pulse Output
Output Mode: Open-collector Optocoupler
Pulse Constant: 10000imp/kWh, Settable
Auxiliary Power Supply
AC/DC 85–265V
DC 24V ±20%
DC 48V ±20%
Power Consumption: ≤10VA
Environment
Operating Temperature: -25°C to +65°C
Storage Temperature: -40°C to +80°C
Humidity: ≤93%RH, Non-condensing
Altitude: ≤2500m
| Parameter | Specification |
|---|---|
| System | 3-phase 4-wire |
| Frequency | 45–65Hz |
| Rated Voltage | AC 3×57.7V/100V, AC 3×220V/380V |
| Voltage Overload | 1.2× rated value continuously; 2× rated value for 1s |
| Voltage Power Consumption | <0.5VA |
| Rated Current | AC 1A or 5A |
| Current Overload | 1.2× rated value continuously; 10× rated value for 1s |
| Current Power Consumption | <0.5VA |
| Voltage Accuracy | Class 0.2 |
| Current Accuracy | Class 0.2 |
| Active Power Accuracy | Class 0.5 |
| Reactive Power Accuracy | Class 1.0 |
| Active Energy Accuracy | Class 0.5 |
| Reactive Energy Accuracy | Class 1.0 |
| Frequency Accuracy | ±0.05Hz |
| Digital Input | 2DI, dry contact input |
| Relay Output | 2DO, normally open contact |
| Relay Contact Capacity | AC 250V/3A; DC 30V/3A |
| Energy Pulse Output | 1Ep, open-collector optocoupler |
| Pulse Constant | 10000 imp/kWh, settable |
| Communication | RS485 |
| Protocol | Modbus-RTU |
| Baud Rate | 1200–38400bps |
| Auxiliary Power Supply | AC/DC 85–265V; DC 24V ±20%; DC 48V ±20% |
| Power Consumption | ≤10VA |
| Operating Temperature | -25°C to +65°C |
| Storage Temperature | -40°C to +80°C |
| Humidity | ≤93%RH, non-condensing |
| Altitude | ≤2500m |
| Insulation Resistance | >100MΩ |
| Faceplate Size | 75 × 75mm |
| Panel Cutout | 67 × 67mm |
| Depth | 94.3mm |
| Function | AMC72-E4/KC (2DI+2DO) |
|---|---|
| Three-phase Voltage | ✓ |
| Zero-sequence Voltage | ✓ |
| Three-phase Current | ✓ |
| Zero-sequence Current | ✓ |
| Three-phase Active Power | ✓ |
| Total Active Power | ✓ |
| Three-phase Reactive Power | ✓ |
| Total Reactive Power | ✓ |
| Three-phase Apparent Power | ✓ |
| Total Apparent Power | ✓ |
| Three-phase Power Factor | ✓ |
| Total Power Factor | ✓ |
| Frequency | ✓ |
| Voltage Phase Angle | ✓ |
| Voltage Unbalance | ✓ |
| Current Unbalance | ✓ |
| Forward / Reverse Power | ✓ |
| Four-quadrant Energy Metering | ✓ |
| System Time Display | ✓ |
| 2 Digital Inputs (DI) | ✓ |
| 2 Relay Outputs (DO) | ✓ |
| Energy Pulse Output (Ep) | ✓ |
| RS485 Communication | ✓ |
| Modbus-RTU | ✓ |
| Event Record (SOE) | — |
| Harmonic Measurement (H) | — |
| Analog Output | — |