Communication
RS485
(Modbus-RTU)
8 digits LCD display U, I, P, Q, PF, kWh, Power measure(999999.99kWh)
AC220
10(80)A
Measurement ①: 1-phase AC kWh
Measurement ②: U,1, P, Q, S, PF, F and etc
Display: LCD Display
HMI: Keypads Progarmming
Communication: RS485 (MODBUS-RTU)
Multi-rate/tariff: 4 Tariff Rates and etc
Pulse Output: Active Pulse Output
Rated Voltage: 220~264Vac L-N
Rated Current: 10(80)A AC
Frequency: 45~65 Hz
Wiring: 1-phase 2-wire
Accuracy: 1.0%(kWh)
Temperature: -25°C~+55°C
Humidity: ≤95% RH
Altitude: ≤2500m
Rated Voltage: 220~264Vac L-N
Rated Current: 10(80)A AC
Frequency: 45~65 Hz
Wiring: 1-phase 2-wire
Accuracy: 1.0%(kWh)
Temperature: -25°C~+55°C
Humidity: ≤95% RH
Altitude: ≤2500m
Acrel ADL200 single phase power meter installing
Note: DIN 35 mm rail installation.
Communication RS485 (Modbus-RTU)
| Parameter | Value |
|---|
DIN-rail mounted. Send us the rated values of your circuit and the supply voltage; we confirm the ordering code, wiring diagram and register list within one working day.
| Input voltage | Reference voltage | AC 220V |
| Voltage range | AC 75~260V | |
| Reference frequency | 50Hz | |
| Power consumption | <10VA | |
| Input current | Basic current | 10A |
| Maximum current | 80A | |
| Starting current | 4‰Ib | |
| Consumption | <4VA | |
| Measurement performance | Accuracy of measuring | 1 class |
| Range of measuring | 000000.00~99999999kWh | |
| Clock accuracy | Error≤0.5s/d | |
| Active pulse | Pulse width | 80±20ms |
| Pulse constant | 1000imp/kWh | |
| Communication | Interface | RS485(A+, B-) |
| Connection mode | Shielded twisted pair conductors | |
| Protocol | MODBUS-RTU | |
| Temperature range | Work temperature | -25℃~55℃ |
| Storage Temperature | -40℃~70℃ | |
| Relative humidity | ≤95%(No condensation) | |
| Altitude | <2000m | |
2.1 Basic & Optional Function
| Function | Function description | Function provide |
| Measurement of kWh | Single-phase active kWh (positive and negative)
| ■ |
| Measurement of electrical parameters | Voltage, Current, Active power, Reactive power, Apparent power, Power factor and Frequency | ■ |
| LCD Display | 8 bits section LCD display | ■ |
| Key programming | 3 keys to set parameters like code, address, baud rate, multi-tariff and communication protocol | ■ |
| Pulse output | Active energy pulse output | ■ |
| Multi-tariff | Date and time 3 months historical energy data frozen storage; Adapt 8 time zones, 8 time interval lists, 14 time interval by day and 8 tariff rates | □F |
| Communication | Communication interface: RS485, Communication protocol: MODBUS-RTU | ■ |
(■: Standard; □: Optional)