Is Your Maximum Demand Averaged Over 30 Minutes?


Malaysia · Maximum demand · APM521
Is Your Maximum Demand Averaged Over 30 Minutes?

A meter can compute demand correctly and still disagree with the bill. One setting explains most of it: the averaging window.

01 · The bill

The bill uses 30 minutes

TNB bills maximum demand over a 30-minute window. The month’s highest half-hour average sets the charge, and since July 2025 that charge has sat inside RP4. The meter has its own demand register — and its window is whatever someone typed into the menu.

Billing window
30 minutes — the month’s highest half hour. TNB tariff schedule ↗
Unit
kW, on medium-voltage TOU accounts
Peak window
Weekdays 14:00–22:00
Meter register
Width and period are separate settings on the APM521 ↗
apm521-01-bill-logic


02 · The arithmetic

A shorter window reads higher

Averaging over a finer interval cannot give a lower maximum. A five-minute surge vanishes in the half-hour figure and shows up in a 15-minute register. The meter is not wrong — it is answering a different question, in the direction that costs money.

Window What the register reports
15 min Equal or higher than the bill — clearly higher on spikey loads.
30 min The billed quantity, if the point and the clocks match.
1–5 min Events, not billing.
apm521-02-two-windows


03 · The setting

Set the period to 30

On the APM521, width is the refresh step and period is the averaging window. Width runs 1 to 5 minutes; period runs 5 to 60 and must be an integer multiple of the width. Set the period to 30 and the register reports what TNB bills.

Setting For a TNB half hour
Width 5 min — must divide the period
Period 30 min — six sub-windows
Records Maximum demand and last month’s, both with timestamps
Alarm Set from the bill, not from a default
Comms RS485 Modbus-RTU
apm521-03-demand-setting
apm521-04-three-checks
04 · The record

The peak, with its timestamp

A monthly maximum says the bill will be high. A timestamp says which half hour did it — this month and last month. That is the difference between a number and an answer, and the start of acting before the next peak.

The meter reports over RS485 Modbus-RTU. A controller compares PCC power with your threshold; storage acts. The meter stays the data source — see the control side.

apm521-05-data-path
apm521-06-meter
Before you specify
Send the bill and the meter model.
We check the demand period, the measurement point and the CT ratio against the bill.