Acrel wireless temperature monitoring is used in high- and low-voltage power systems to watch every electrical contact continuously, so that a loosening joint or an overloaded busbar is found before it trips a feeder. Because the sensors are wireless, the system can be added to a switchgear line-up that is already in service.
Two ways to read the temperature
Local display uses units such as ATP007 and ARTM-Pn, which show each sensor channel on the panel door. Online monitoring sends the same channels to a gateway and then to the Acrel IoT platform, where limits are set per channel and alarms are logged with a time stamp. Every device in the chain speaks RS485 with Modbus-RTU, so a gateway can carry the data onward over 4G, Wi-Fi or Ethernet.

The solution in one page: sensors on the contacts, receivers in the panel, platform above.
The wireless link, in numbers
ATC600 series transceiver
| Parameter | Value |
|---|---|
| Function | Receiver or repeater for wireless temperature sensors |
| Models | ATC600-C receiver, ATC600-Z signal booster, ATC600-M receiver, ATC600-PD |
| Wireless frequency | 433 MHz or 470 MHz |
| Communication distance | 150 m open field at 470 MHz; 50 m for the 433 MHz sensor set |
| Matching sensors | ATE400, ATE100, ATE100M, ATE100P, ATE200, ATE200P, ATE210S, AHE100, ACE100; ATC600-M pairs with ATE300M and ATE210M |
| Power source | AC 85-265 V, DC 100-300 V or DC 12-48 V |
| Backward communication | RS485, Modbus-RTU frame with CRC16 |
| Mounting | Inside the LV or MV switchgear panel |
What the sensors sit on
- Cable heads and busbar joints in a low-voltage drawer or a capacitor cabinet.
- Busbar connectors in a rising main, where a hot joint is the usual start of a smoke event.
- Breaker contacts and disconnectors in a medium-voltage cubicle, including the live parts that an infrared gun can only reach during a shutdown.
A surface sensor cannot be fitted to a live busbar. The sensor type is chosen with the panel design, so send the drawing before we quote a set.
Tell us the number of panels, the voltage class, how many contacts per panel and whether you want a local display, a gateway to the cloud platform, or both. We return a sensor and transceiver list with the wiring diagram within one working day.
Related products: ATC600 wireless transceiver · ARTM-8 temperature controller · AWT100 gateway
Post time: Mar-22-2024