ob_start_detected
head_banner_news

Dashboards Do Not Dispatch – What a Microgrid Coordination Controller Actually Does


Microgrid · Control Layer · Coordination Controller

Dashboards Do Not Dispatch — What a Microgrid Coordination Controller Actually Does

A site installs a monitoring platform, the dashboard looks impressive, and the energy bill does not move. The reason is the same every time: a platform shows what happened; something else must decide what happens next.

Why the dashboard is not enough

Cloud platforms are good at four things: storing data, drawing it, comparing periods and sending alarms. They are not good at deciding, for three practical reasons:

Latency
A second is a long time
A decision needed within a second cannot wait on a round trip to a data centre
The control loop has to close on site
Consequence
Read, or write?
Reading a value and writing commands into plant are different risk profiles
One is safe to do remotely; the other is not
Continuity is the third reason: a remote site must behave sensibly when the internet is unavailable.

The architecture that resolves this is standard: the cloud layer analyses and reports, the edge layer decides and commands, the field layer measures and executes. A platform reads and reports; a controller decides. That single distinction separates a site that looks good on a screen from one whose energy bill actually falls.

A4_IMG1_cloud_vs_loop

Three layers, three different jobs

Reaction time separates the three layers, and that decides which layer a function belongs on.

Which layer does what
Cloud · seconds to minutes AcrelEMS 3.0 — multi-site visibility, analysis, demand reporting, alarms
Edge · milliseconds to seconds ACCU controller, Acrel-2000MG — runs the strategy, issues charge and discharge commands, keeps running when the link is down
Field · milliseconds Storage cabinet, PV inverter, meters, protection relays — measures, protects and executes
A platform reads and reports; a controller decides and commands.

The controller runs a loop on a fixed cycle, and every step is local.

Dispatch loop
01
Acquire
PCC power, state of charge, PV output, generator status and changeover position.
02
Compare
Against the strategy: demand threshold, planned curve, SOC limits, time-of-use window.
03
Decide
A setpoint — discharge, charge, hold, start or stop the generator.
04
Command
Over the protocol each device speaks, and confirm acceptance.
05
Record
Events logged locally for the platform.

A4_IMG2_three_layers

The strategies it runs

The value is not the controller but the strategies it executes, and how cleanly they change when the economics change. Six are common:

01
Demand threshold control
Monthly maximum demand charge; time-of-use factories.
02
Planned charge and discharge curve
Peak / off-peak price spread.
03
PV self-consumption priority
Rooftop PV where export is limited.
04
Anti-reverse-flow
Export restriction compliance.
05
Generator dispatch and SOC protection
Off-grid sites with a standby generator.
06
On / off-grid switching
Supply continuity.

A controller is only useful if it can talk to the equipment on site, which rarely comes from one supplier. The ACCU series supports Modbus RTU and Modbus TCP, IEC 60870-5-101 / 103 / 104 and MQTT, with RS485, CAN, Ethernet and 4G interfaces and digital inputs and outputs. The digital I/O lets the controller operate a changeover or read a breaker status directly. At site level, Acrel-2000MG monitors and controls PV, storage, charging and loads together; above both, AcrelEMS 3.0 provides the cloud view.

A4_IMG3_strategies

Choosing between the models

Three questions decide most of it, and getting them right at quotation stage is cheaper than discovering them on site.

01
Number of devices
Count every PV inverter, storage unit, meter, protection relay and generator controller, then add spare capacity for later additions.
02
Protocols in use
Confirm the existing equipment speaks a supported protocol, or that a gateway is available.
03
Hard-wired I/O
Changeover control, breaker status, generator start signal and alarm contacts all need digital inputs and outputs.

Ask for the strategy configuration manual and a third-party type test report for the exact model you specify. The controller does not depend on the platform to keep operating: it runs its strategy locally, stores data on site and forwards it when the link returns — on a remote site, that is the difference between a working system and one that is not.

CHECK DEVICE BY DEVICE  Third-party inverters and batteries integrate over Modbus RTU / TCP, IEC 60870-5-101 / 103 / 104 or MQTT — whether a specific device works depends on the register map it exposes.

A4_IMG4_product_selection

Next step
Send us your single-line diagram and device list.

With the single-line diagram, the devices to be coordinated and the strategies you want to run, we can specify the controller, confirm protocol compatibility and set out what commissioning will involve.

Request a control review

This article is technical information, not a commercial offer. Protocol support and interface counts are taken from Acrel published literature for the ACCU series. Certification and type test reports are issued per model; confirm the applicable document for the model you specify. Local approval in Malaysia should be confirmed with the relevant authority.


Post time: Oct-15-2026