
Accuracy
Active energy: Class 0.5
Auxiliary power supply
AC 220V
Consumption
Current: Power consumption< 0.5VA;
Auxiliary power supply: power consumption≤5VA
Installation
Panel mounted
Dimension(L*W*H)
Panel size (L×W): 75*75mm
Cutout(L×W): 67*67mm
Housing (L×W×H): 66*66*94.3mm
Switch relay
DC 30V/3A AC 220V/3A
Starting current
0.3%
Accuracy Active energy: Class 0.5 Auxiliary power supply AC 220V Consumption
| Parameter | Value |
|---|---|
| Current | Power consumption< 0.5VA; Auxiliary power supply: power consumption≤5VA |
Panel-mounted. Send us the rated values of your circuit and the supply voltage; we confirm the ordering code, wiring diagram and register list within one working day.
| Technical parameter | Value | |||
| Input | Rated value | AC voltage: Single phaseAC 100V,400V Three phaseAC 100V,400V,660V(UL-L, Only 72/ 96) AC current: AC1A,5A; DC voltage: 1000V,300V,75mV,10V; DC current: 0-20mA,4-20mA,5A; | ||
| Overload | Voltage: 1.2 times rated value(continuous); 2 times rated value /1 second Current: 1.2 times rated value(continuous); 10 times rated value /1 second | |||
| Frequency | 45Hz~65Hz | |||
| Power consumption | Power consumption of each voltage, current input circuit is less than 0.5VA | |||
| Accuracy | 0.5 class | |||
| Function | Display | LED or LCD | ||
| Communication | RS485, Modbus-RTU protocol;(1 start bit,8 data bit,1 stop bit, no parity) Baud Rate 2400/4800/9600/19200 bps etc. | |||
| Alarm | 1 channel passive relay, contact capacity 3A/30VDC,3A/250VAC, Used for high, low, unbalance alarm etc. | |||
| Analog | DC4~20mA,( load <500Ω) (note: Shielded wire is specially selected for the above signal input and output) | |||
| Switching | Input | 4 channel or 2 channel dry contact Input, built in power supply | ||
| Output | 2 channel switching output, NO relay contact, capacity: 3A/30VDC,3A/250VAC | |||
| Auxiliary supply | Voltage range | AC/DC 85-265V | ||
| Power consumption | <5VA | |||
| Insulation resistance | ≥ 100MΩ | |||
| Power frequency withstand voltage | Between power supply set of terminals and signal input, output set of terminals 2kV/1min (RMS) Between the shell and all set of terminals(except the set of terminals reference voltage less than 40V) AC 4kV | |||
| Environment | Temperature | Operation: -10℃~+55℃Storage: -25°C ~+70°C |
| Humidity | ≤95%RH, no condensation, without corrosive gas | |
| Altitude | ≤ 2500m |
2.1 Basic & Optional Function
| Type | Basic function | Shape | Optional function |
| AMC48-AI AMC48-AV | Current, voltage measurement; LED | 48 Square | RS485 communication (/C ) Analog output (/M ) |
| AMC48-AI3 AMC48-AV3 | None | ||
| AMC48L-AI AMC48L-AV | Current, voltage measurement; LCD | 1. RS485 communication (C) 2. Analog output (M) | |
| AMC48L-AI3 AMC48L-AV3 | None | ||
| AMC72-AI AMC72-AV AMC72-AI3 AMC72-AV3 | Current, voltage measurement; LED | 72 Square | 1. RS485 communication (C) 2. Analog output (M) 3.Alarmoutput (J) 4.Analog output + RS485 communication (MC) 5. RS485 communication + switching output 2DI2DO (KC) 6.Alarm output + analog output +RS485 communication (JMC) |
| AMC72-DI AMC72-DV | DC voltage, current measurement; LED | ||
| AMC72L-AI AMC72L-AV AMC72L-AI3 AMC72L-AV3 | Current, voltage measurement; LCD | ||
| AMC72L-DI AMC72L-DV | DC voltage, current measurement; LCD | ||
| AMC96-AI AMC96-AV AMC96-AI3 AMC96-AV3 | Current, voltage measurement; LED |
96 Square | 1. RS485 communication (C) 2. Analog output (/M or 3M) 3.Alarm output (J) 4.Analog output + RS485 communication (MC or M3C) 5. RS485 communication + switching 4DI2DO (KC) |
| AMC96L-AI AMC96L-AV AMC96L-AI3 AMC96L-AV3 |
Current, voltagemeasurement; LCD |
Note:
1. AI/AV means single-phase current/voltage, AI3/AV3 means three-phase current/voltage.
2. /J means 1 channel relay output (multiplexing with second channel switching output).