ADW600 Modular Multi-Circuit Energy Metering System

Application:

ADW600 is designed for centralized multi-circuit metering in low-voltage distribution panels. It is suitable for factories, commercial buildings, data centers, telecom facilities, charging infrastructure and retrofit projects where multiple outgoing circuits must be monitored with minimal panel modification.

 

Basic Parameters:

Modular architecture with ADW600-M gateway, ADW600-U voltage module and ADW600-I current modules; up to 12 three-phase four-wire circuits per gateway; split-core CT options up to 600 A; Class B active energy; 35 mm DIN-rail installation; optional 4G, Ethernet or Wi-Fi gateway communication.


Information

Parameter

Function

Download

Characteristic

ADW600 Characteristic

Multi-Circuit Metering
Up to 12 Three-Phase Circuits

ADW600 Characteristic

Communication
RS485 (Modbus-RTU)
Optional 4G / WiFi / Ethernet

ADW600 Characteristic

Modular Design
Voltage, Current, I/O,
Temperature & Residual Current Modules

Main Functions

02_ADW600_Complete_System_Rear

Measurement ①: U, I, P, Q, S, PF, F

Measurement ②: Forward & Reverse Active Energy, Four-Quadrant Reactive Energy

Multi-Circuit: Independent Multi-Circuit Energy Metering

Harmonics: Total Harmonic & 2nd–31st Harmonics

Communication: RS485 (MODBUS-RTU)

Wireless / Network Communication: Optional 4G / WiFi / Ethernet

I/O Extension: Optional 4DI / 2DO

Temperature Monitoring: Optional 12-Channel Temperature Measurement

Residual Current: Optional 4-Channel Residual Current Measurement

Installation: 35mm DIN Rail

Main Parameters

Rated Voltage: 3×57.7/100V, 3×220/380V, 3×100V, 3×380V

Input Current:
D10: 0.03–0.15(6)A
D16: 0.8–2(100)A
D24: 3.2–8(400)A
D36: 4.8–12(600)A

Frequency: 45–65Hz

Voltage Accuracy: ±0.5%

Active Energy Accuracy: Class B

01_ADW600_Complete_System_Front (1)
02_ADW600_Complete_System_Rear

Communication: RS485 (MODBUS-RTU)

Optional Communication: 4G / WiFi / Ethernet

Working Temperature: -25°C to +55°C

Humidity: ≤95% RH, No Condensation

Altitude: <2000m

Installation: Standard 35mm DIN Rail

Dimension

03_Appearance_and_Dimensions_EN

Wiring

05_Voltage_and_Current_Wiring_EN
06_Digital_IO_Temperature_Leakage_Wiring_EN

Multi-Circuit Metering Up to 12 Three-Phase Circuits

  • Output

    RS485 (MODBUS-RTU) Wireless / Network

    Modbus-RTU into your EMS / SCADA

  • Output (optional)

    4G / WiFi / Ethernet

  • System voltage

    3×57.7/100V, 3×220/380V, 3×100V, 3×380V

  • Voltage accuracy

    ±0.5%

Technical data

ParameterValue
Measurement ①U, I, P, Q, S, PF, F
Measurement ②Forward & Reverse Active Energy, Four-Quadrant Reactive Energy
Multi-circuitIndependent Multi-Circuit Energy Metering
HarmonicsTotal Harmonic & 2nd–31st Harmonics
Temperature MonitoringOptional 12-Channel Temperature Measurement Residual
CurrentOptional 4-Channel Residual Current Measurement
Installation35mm DIN Rail
Input currentD10: 0.03–0.15(6)A D16: 0.8–2(100)A D24: 3.2–8(400)A D36: 4.8–12(600)A
Frequency45–65Hz
Active energy accuracyClass B
Working temp.-25°C to +55°C
Humidity≤95% RH, No Condensation Altitude: <2000m

Built-in functions

  • Communication RS485 (Modbus-RTU) Optional 4G / WiFi / Ethernet
  • Modular Design Voltage, Current, I/O, Temperature & Residual Current Modules

DIN-rail mounted; communication wireless M-Bus / RF. Send us the rated values of your circuit and the supply voltage; we confirm the ordering code, wiring diagram and register list within one working day.


  • Previous:
  • Next:

  • ADW600 main function by module
    ADW600-M Data collection and remote transmission over 4G, Ethernet or WiFi
    ADW600-U Voltage measurement and sampling
    ADW600-I Active energy metering (positive, reverse) and quadrant reactive energy; voltage, current, power factor, frequency, active, reactive and apparent power; total harmonic content and 2nd to 31st sub-harmonics; pulse output of active energy
    ADW600-K 4 digital inputs and 2 digital outputs
    ADW600-TL 12 channels of temperature measurement and 4 channels of residual current measurement
    Electrical characteristics
    ADW600-U rated voltage 3×57.7/100 V, 3×220/380 V, 3×100 V, 3×380 V
    Voltage accuracy 0.5%
    Frequency range 45-65 Hz
    Voltage power consumption <0.5 VA per phase
    ADW600-I input current D10 0.03-0.15(6) A; D16 0.8-2(100) A; D24 3.2-8(400) A; D36 4.8-12(600) A
    Active energy accuracy B class
    Energy pulse width 80 +/- 20 ms
    Active energy pulse constant D10 6400 imp/kWh; D16 400 imp/kWh; D24 100 imp/kWh; D36 60 imp/kWh
    Current power consumption <1 VA per phase
    ADW600-K digital input 4-channel passive input with built-in DC12 V power supply
    ADW600-K digital output 2-channel passive output, capacity AC230 V / DC30 V, 3 A