head_banner_pro

ADL200N-CT Single Phase MID UL Energy Meter

●Measure bidirectional voltage, current, power, forward and reverse power in AC system

●80A, 120A,200A,300A input

●RS485(MODBUS-RTU)

●Certification: CE, MID, UL, RoHS

●DIN 35 mm


Information

Parameter

Download

General

    ADL series DIN-rail mounted multifunctional electric energy meter is an intelligent instrument mainly designed for new energy power generation systems such as photovoltaic grid-connected system, micro inverter system, energy storage system, AC coupling system, etc. The product has the advantages of high precision, small volume, high respondent speed and convenient installation. The product has the features of sampling, metering and monitoring power parameters, communicating with an inverter or an energy management system (EMS), realizing the functions of preventing reverse flow, regulating power generation, charging and discharging batteries according to real-time power and accumulated electric energy, and realizing bidirectional metering and household distributed photovoltaic energy management. 

Function

 Input voltage
    230VAC

 Inputr current
     80A, 120A, 200A, 300A

 Response rate
     ≤100ms

XSX06094
XSX06096
√ Installation
      35mm Din-rail method
 
 Dimension(L*W*H)
      90*18*65mm

Wiring

未标题-29

Structure

1741326840051

Related Products

DTSD1352-C

Three-phase solar energy meter

ACR10R-DxxTE

Single-phase solar energy meter

ADL400N-CT

Three-phase solar energy meter


  • Previous:
  • Next:

  • 1. Technical parameter

    Item Performance Parameters
    Model Series ADL200N-CT ADL400N-CT
    Measurement Grid Single-phase Three-phase four-wire, three-phase three-wire, single-phase three-wire
    Voltage Rated voltage 230V Three-phase: 3×220/380V、3×230/400V、3×277/480V 
    Input Range ±20%
    Overload 1.2 times rating (continuous)2 times the rating for 1 second
    Power consumption <0.2VA
    Accuracy class Error ±0.5%
    Current Input current 80A, 120A, 200A, 300A 3×80A, 3×120A, 3×200A, 3×300A
    Overload 1.2 times rating (continuous)2 times the rating for 1 second
    Power consumption <0.2VA
    Accuracy class Error ±0.5%
    Power Active, reactive, apparent power, error ±0.5℅
    Grid frequency 45~65Hz, error ±0.5%
    Response rate ≤100ms (voltage, current, power)
    ≤1s (electrical energy)
    Metering Electric energy Active energy :Class B (split current transformer)Reactive energy (Class 2 accuracy)
    Electromagnetic Compatibility Electrostatic discharge immunity class III
    Electrical fast transient burst immunity class IV
    Surge (shock) immunity Class IV
    Security Power frequency withstand voltage Between communication and signal input, AC4kV 1min
    Insulation resistance Input and output terminals to casing >100MΩ
    Communication Interface and communication protocol RS485 interface and Modbus RTU protocol
    Communication address range Modbus RTU:1~ 247;
    Baud rate Support 1200bps-38400bps
    Environment Operating temperature -40℃~+70℃
    Storage temperature -40℃~+70℃
    Relative humidity ≤95℅ (without condensation)
    Altitude ≤3000m
    Write your message here and send it to us